background image

 

 

 

 

5

 

Undo the four screws at the corners of the housing. The control electronics are mounted on the 
enclosure cover. Using proper fixing, the controller enclosure can be screwed to the wall with 
cable entry grommets downwards.   

 

Caution:

 Controller wiring should only be done when the unit is not energized. It is possible to 

damage the control unit if it is assembled under voltage. Miniaturized terminal blocks are used for 
making wiring connections. The wire is held in place within the terminal with a screw that provides 
excellent contact without damage to the wire. 

 

Cable Connection: 

A small blade screwdriver may be used to fasten miniaturized terminal 

block screws while the corresponding wire is inserted.

  

 

Use up to an 18 AWG stranded wire to connect the sensor  cables to the unit. The 

KS

 terminal 

should be connected to the 

collector sensor

 (higher temperature); the 

BS

 terminal is designated 

for the 

return sensor

 (lower temperature). 

 

 

 
 
 

ower Connections: 

A small blade screwdriver may be used to fasten miniaturized 

terminal block screws while the corresponding wire is inserted.  

 
NOTE 1: 

Always disconnect the controller from power supply before opening the housing.  

 

NOTE 2:

 

The controller should be properly grounded. 

Flexible wires, 18/3 AWG 

(gauge/conductor), simplify connection to the terminals.

 The power terminal block will 

accommodate wire sizes to 14 AWG. All other connections should be secured and adequately 
tightened, as loose power connections will over-heat, and may cause fire.  
 
NOTE 3: It is important that the specified output loads (245 Watts) are not exceeded. Where 
these loads expect to exceed, external relays must be used. Always keep power cables away 
from sensor cables and other low voltage signal cables. 
 
NOTE 4: To protect against lightning damage, the system must be grounded according to local 
regulations. Sensor failures due to the weather or electrostatic are mostly due to poor grounding. 
 

 
 
 

ROUBLESHOOTING 
 

Problem: 

Nothing happens when unit is powered-up. 

Cause/Remedy:

 The fuse could be blown  – check and replace if necessary. If the fuse blows 

again, then the pump draws more current than the unit is design to supply. Use an auxiliary relay 
or contact your product supplier. 
 
 

Problem: 

One or more LED’s is fluctuating. 

Cause/Remedy: 

This indicates a system alarm warning, which may be caused by a sensor fault: 

• 

Lower Collector LED blinks 

è

 Collector sensor cable is short circuited  

• 

Lower Storage Tank (70 

o

F) LED blinks 

è

 Return sensor cable is short circuited 

• 

Upper Collector LED blinks 

è

 Collector sensor cable is open 

• 

Upper Storage Tank (200 

o

F) LED blinks 

è

 Return sensor cable is open 

P

 

T

 

Summary of Contents for USDT 2005

Page 1: ...l unit has the following functions 2 inputs for temperature sensors Suitable for sensors of type Thermistor and PT1000 Adjustable 70 o F to 210 o F overheating protection Adjustable 4 o F to 24 o F temperature difference delta T Manual override of pump for system testing Symbolic display of all parameters Indications of current state of pump System status and diagnostic displays Collector sensor s...

Page 2: ...T to avoid pump cycling The pump A1 runs only when the temperature at the collector sensor location S1 is higher than the return temperature at location S2 by at least T The pump stops if T is less than the preset value or the if the temperature at location S2 storage tank has reached the TMAX A1 ON only when S1 S2 diff S2 max Boiler Control L Mode The User can switch USDT 2005 to operate a boiler...

Page 3: ...med under voltage Switch Positions S K Solar systems with KTY 2000 ohm sensors S P Solar systems with PT 1000 1000 ohm sensors L K Boiler control with KTY 2000 ohm sensors L P Boiler control with PT 1000 1000 ohm sensors The impedance characteristics of sensors temperature dependencies are represented in the following table T 0 10 20 25 30 40 50 60 70 80 90 100 C R KTY 1630 1772 1922 2000 2080 224...

Page 4: ...om the power supply before removing the cover Never leave the unit unattended if the cover has been removed and the power supply is connected 5 Do not exceed unit ratings of 2 15 amps 1 6 HP or 245 Watts pump 6 It is advisable to route power cables away from sensor cables ensor installation Temperature sensors may be installed in fluid lines by mounting in a tee or strapping it to the piping direc...

Page 5: ...0 ft A connection between the sensor and extension can be established as follows Cut supplied heat shrinkable tubing to desired length about Slide tubing over one end of wire to be sliced after removing enough outer insulation to accept the tubing Then splice wire and slide tubing over the splice Heat gently all around until tubing shrinks tight Slide larger tubing about over the entire completed ...

Page 6: ...erly grounded Flexible wires 18 3 AWG gauge conductor simplify connection to the terminals The power terminal block will accommodate wire sizes to 14 AWG All other connections should be secured and adequately tightened as loose power connections will over heat and may cause fire NOTE 3 It is important that the specified output loads 245 Watts are not exceeded Where these loads expect to exceed ext...

Reviews: