3/4

 

dPo

First defrost after start-up: (y = immediately; n = after the IdF time)

 

dAF

Defrost delay after continuous cycle: (0

÷

23.5h) time interval between

the end of the fast freezing cycle and the following defrost related to it.

FANS
FnC Fans operating mode
C-n= runs with the compressor, OFF during defrost;

o-n = continuous mode, OFF during defrost;
C-Y = runs with the compressor, ON during defrost;
o-Y = continuous mode, ON during defrost;

Fnd Fans delay after defrost: (0÷255min) Time interval between end of defrost and

evaporator fans start.

Fct Temperature differential avoiding short cycles of fans (0÷59°C; Fct=0 function

disabled). If the difference of temperature between the evaporator and the room
probes is more than the value of the Fct parameter, the fans are switched on.

FSt Fans stop temperature: (-50÷50°C/122°F) setting of temperature, detected by

evaporator probe, above which fans are always OFF.

ALARMS

 

ALC  Temperature alarms configuration: (Ab; rE)
Ab= absolute temperature: alarm temperature is given by the ALL or ALU values.
rE = temperature alarms are referred to the set point. Temperature alarm is
enabled when the temperature exceeds the “SET+ALU” or “SET-ALL” values.

ALU MAXIMUM temperature alarm: (SET÷110°C; SET÷230°F) when this

temperature is reached  the alarm is enabled, after the “ALd” delay time.

ALL Minimum temperature alarm: (-50.0 ÷ SET°C; -58÷230°F when this temperature

is reached  the alarm is enabled, after the “ALd” delay time.

 

ALd  Temperature alarm delay: (0÷255 min) time interval between the detection
of an alarm condition and alarm signalling.

 

dAO Exclusion of temperature alarm at startup: (from 0.0 min to 23.5h) time
interval between the detection of the temperature alarm condition after instrument
power on and alarm signalling.

DIGITAL INPUT
i1P Digital input polarity: oP: 
the digital input is activated by opening the contact; CL:

the digital input is activated by closing the contact.

i1F Digital input configuration:

EAL  = external alarm: “EA” message is displayed; bAL = serious alarm “CA”
message is displayed. PAL = pressure switch alarm, “CA” message is displayed;
dor = door switch function; dEF = activation of a defrost cycle; LHt =not enabled;
Htr = kind of action inversion (cooling – heating).

did: (0

÷

255 min)

with  i1F= EAL or i1F = bAL digital input alarm delay: delay between the
detection of the external alarm condition and its signalling.
with i1F= dor: door open signalling delay
with i1F = PAL: time for pressure switch function: 
time interval to calculate the
number of the pressure switch activation.

nPS Pressure switch number: (0 

÷

15) Number of activation of the pressure switch,

during the “did” interval, before signalling the alarm event (I2F= PAL).
If the nPS activation in the did time is reached, switch off and on the
instrument to restart normal regulation.

 

odc

Compressor and fan status when open door:  no = normal; Fan = Fan

OFF; CPr = Compressor OFF; F_C = Compressor and fan OFF.

OTHER
PbC Type of probe:
 it allows to set the kind of probe used by the instrument: PbC =

PBC probe, ntC = NTC probe.

 

dP1

First probe display

 

dP2

Second probe display

 

rEL

Software release for internal use.

 

Ptb

Parameter table code: readable only.

8.

 

DIGITAL INPUT

The free contact digital input is programmable in five different configurations by the “i1F
parameter.

8.1

 

DOOR SWITCH INPUT  (i1F = dor)

It signals the door status and the corresponding relay output status through the “odc
parameter:

no = normal (any change);
Fan = Fan OFF;
CPr = Compressor OFF;
F_C = Compressor and fan OFF.

Since the door is opened, after the delay time set through parameter “did”, the door
alarm is enabled, the display shows the message “dA” and the regulation restarts.
The alarm stops as soon as the external digital input is disabled again. With the door
open, the high and low temperature alarms are disabled.

8.2

 

GENERIC ALARM (i1F = EAL)

As soon as the digital input is activated the unit will wait for “did” time delay before
signalling the “EAL” alarm message. The outputs status don’t change. The alarm stops
just after the digital input is de-activated.

8.3

 

SERIOUS ALARM MODE (i1F = bAL)

When the digital input is activated, the unit will wait for “did” delay before signalling the
CA” alarm message. The relay outputs are switched OFF. The alarm will stop as soon
as the digital input is de-activated.

8.4

 

PRESSURE SWITCH (i1F = PAL)

If during the interval time set by “did” parameter, the pressure switch has reached the
number of activation of  the “nPS” parameter, the “CA” pressure alarm message will be
displayed. The compressor and the regulation are stopped. When the digital input is ON
the compressor is always OFF.
If the nPS activation in the did time is reached, switch off and on the instrument
to restart normal regulation.

8.5

 

START DEFROST (i1F = dFr)

It starts a defrost if there are the right conditions. After the defrost is finished, the normal
regulation will restart only if the digital input is disabled otherwise the instrument will wait
until the “MdF” safety time is expired.

8.6

 

INVERSION OF  THE KIND OF ACTION: HEATING-COOLING (i1F = Htr)

This function allows to invert the regulation of the controller: from cooling to heating and
viceversa.

8.7

 

DIGITAL INPUTS POLARITY

The digital input polarity depends on the “i1P” parameter.
i1P=CL: the input is activated by closing the contact.
i1P=OP: the input is activated by opening the contact

9.

 

INSTALLATION AND MOUNTING

Instrument XR60C shall be mounted on vertical panel, in a
29x71 mm hole, and fixed using the special bracket
supplied.
To obtain an IP65 protection grade use the front panel
rubber gasket (mod. RG-C) as shown in figure.

The temperature range allowed for correct operation is 0

÷

60 °C. Avoid places subject

to strong vibrations, corrosive gases, excessive dirt or humidity. The same
recommendations apply to probes. Let air circulate by the cooling holes.

10.

 

ELECTRICAL CONNECTIONS

The instrument is provided with screw terminal block to connect cables with a cross
section up to 2,5 mm

2

. Before connecting cables make sure the power supply complies

with the instrument’s requirements. Separate the probe cables from the power supply
cables, from the outputs and the power connections. Do not exceed the maximum
current allowed on each relay, in case of heavier loads use a suitable external relay.

10.1

 

PROBE CONNECTION

The probes shall be mounted with the bulb upwards to prevent damages due to casual
liquid infiltration. It is recommended to place the thermostat probe away from air
streams to correctly measure the average room temperature. Place the defrost
termination probe among the evaporator fins in the coldest place, where most ice is
formed, far from heaters or from the warmest place during defrost, to prevent premature
defrost termination.

11.

 

HOW TO USE THE HOT KEY

11.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)

1.

 

Program one controller with the front keypad.

2.

 

When the controller is ON, insert the “Hot key” and push 

9

9

 key; the  "uPL"

message appears followed a by flashing “End”

3.

 

Push “SET” key and the End will stop flashing.

4.

 

Turn OFF the instrument remove the “Hot Key”, then turn it ON again.

NOTE: the “Err” message is displayed for failed programming. In this case push again

9

9

 key if you want to restart the upload again or remove the “Hot key” to abort the

operation.

 
5

Summary of Contents for Jewett XR60C

Page 1: ...Installation and Operation Manual Thermo Scientific Jewett Blood Bank Refrigerators ...

Page 2: ... 2008 Thermo Fisher Scientific All rights reserved Suva is a registered trademark of DuPont All other trademarks are the property of Thermo Fisher Scientific Inc and its subsidiaries ...

Page 3: ...f electrical characteristics other than those specified on the serial plate will cause permanent damage to the mechanism The serial plate is located inside the refrigerator at the top of the right hand wall 7 All models have been provided with an electric condensate evaporator located on the back of the cabinet Periodic cleaning of the condensate pan will insure proper operation CAUTION PAN AND HE...

Page 4: ...djust any control parameters it is advisable to contact Technical Service before doing so CAUTION Unless a front panel control option has been specified the control panels for BBR blood bank refrigerators are located inside a junction box on the back of the refrigerator To access the control remove the four screws and carefully remove the cover Be sure to avoid touching any component inside the ju...

Page 5: ...CONTROLLING LOADS 3 1 COMPRESSOR The regulation is performed according to the temperature measured by the thermostat probe with a positive differential from the set point if the temperature increases and reaches set point plus differential the compressor is started and then turned off when the temperature reaches the set point value again In case of fault in the thermostat probe the start and stop...

Page 6: ...than 3s the POF message will be displayed 6 7 TO UNLOCK THE KEYBOARD Keep pressed together for more than 3s the 9 9 and 8 8keys till the Pon message will be displayed 6 8 THE CONTINUOUS CYCLE When defrost is not in progress it can be activated by holding the 9 9 key pressed for about 3 seconds The compressor operates in continuous mode for the time set through the CCt parameter The cycle can be te...

Page 7: ...pened after the delay time set through parameter did the door alarm is enabled the display shows the message dA and the regulation restarts The alarm stops as soon as the external digital input is disabled again With the door open the high and low temperature alarms are disabled 8 2 GENERIC ALARM i1F EAL As soon as the digital input is activated the unit will wait for did time delay before signall...

Page 8: ...5 C 0 7 C 1 digit 14 CONNECTIONS 14 1 XR60C 12VAC DV OR 24 VAC DV N C Line 8 3 A250Va 8 3 A Max 16A Comp Def Fan E va p R oo m Hot Key NOTE The compressor relay is 8 3 A or 16 6 A according to the model 24Vac dc supply connect to the terminals 7 and 8 14 2 XR60C 120VAC OR 230 VAC N C Line 8 3 A250Va 8 3 A Max 16A Comp Def Fan E va p R oo m Hot Key NOTE The compressor relay is 8 3 A or 16 6 A accor...

Page 9: ... of slides DRAWER SLIDE MOUNTING INSTRUCTIONS 1 Push into slots in rear standard as shown in Step 1 Make certain that the opposite drawer slides are in the same slots in the opposite standards 2 Push into slots in front standard and press down as shown in Step 2 If necessary tap into place 7 SHELVES OPTIONAL Units for which optional shelves have been ordered come with shelves pre installed at the ...

Page 10: ...e to removal of the dollar bill test strip should be felt Check the perimeter of the door If the latch is loose see latch adjusting information 5 Replace cover plate A Note To accomplish different offsets shims are utilized If replacing hinges make sure to reuse any shims furnished on the cabinet 8 2 Latch and Strike Adjustment 1 Latch is fastened to door 2 For up or down adjustment proper latch e...

Page 11: ...ese RoHS Anweisungfallen finden Sie unter www thermo com Conformità WEEE Questo prodotto deve rispondere alla direttiva dell Unione Europea 2002 96EC in merito ai Rifiuti degli Apparecchi Elettrici ed Elettronici WEEE È marcato col seguente simbolo Thermo Fischer Scientific ha stipulato contratti con una o diverse società di riciclaggio smaltimento in ognuno degli Stati Membri Europei Questo prodo...

Page 12: ...e information can be found on the dataplate attached to the equipment If available please provide the date purchased the source of purchase manufacturer or specific agent rep organization and purchase order number IF YOU NEED ASSISTANCE SALES DIVISION Phone 1 866 984 3766 1 866 9 THERMO LABORATORY PARTS and SERVICE Phone 1 800 438 4851 TECHNICAL SUPPORT Phone 1 800 438 4851 ...

Page 13: ...Thermo Fisher Scientific Inc 275 Aiken Road Asheville NC 28804 United States www thermofisher com 306098H01 Rev E ...

Reviews: