All installations and services must be performed by qualified service personnel.
7
NOTE:
If this furnace replaces an appliance with a vent that was originally installed in a common vent system serving other
appliances, the vent system is likely now too large to properly vent the remaining appliances only and must be modified
accordingly. Refer to Natural Fuel Gas Code Appendix G Category I vent tables for common venting a PG Series furnace
and another fan assisted or natural draft unit.
In order too common vent a PG Series furnace with a natural draft gas fired hot water heater; follow the recommendation of
the NFGC Category I venting tables.
If the NFGC venting tables do not apply to a specific common venting system then refer to the section on replacing an
existing furnace from a common vent in Section G of this manual.
NOTICE:
Thermo Pride power gas units may be sidewall vented with a power sidewall venting system that is appropriate
for the application and certified by a nationally recognized testing agency for use with gas fired warm air central furnaces.
NOTICE:
An agency approved gas barometric control or draft diverter
must
be installed. The draft control device must
also meet the approval of the local authorities. See the draft control manufacturers instructions for installation.
E. VENT DAMPERS
If a vent damper is installed, it must be certified by a nationally recognized testing agency. It must be an electro-
mechanical type that opens completely before gas flows to the main burner and closes only after the gas valve has
shut off gas flow to the main burner.
WARNING:
The PG Series furnaces must not be installed with a manual or thermally actuated vent damper.
F. CONDENSING IN THE CHIMNEY:
Due to the increasing efficiencies of our furnaces, more heat is being placed into the home instead of up the chimney.
This means that the stack temperature will be lowered which may result in condensing within the chimney under
certain conditions. The following is an explanation on why and what to do if condensing occurs.
Moisture occurs in flue gases when hydrogen is mixed with oxygen from the chemical reaction produced by
combustion. This mixture of hydrogen and oxygen produces water molecules.
The flue gas vapor may do one of two things as it escapes up the chimney:
1. Remain in a vapor state if the internal chimney wall temperature is above the dew point, or
2. Condense on the chimney walls if they are chilled below the dew point.
Condensing will always occur on chimney walls whose temperatures are below the dew point, but will evaporate
once the walls are warmer than the dew point. If the chimney walls do not reach the dew point during the cycle of the
furnace, the moisture may accumulate in large enough quantities to cause problems such as corrosion of the chimney
or corrosion of the heat exchanger.
This condensation most likely will not occur at the bottom of the chimney, because the flue gas is heating the
chimney walls as it rises and the bottom will be heated first. This heating of the walls will cause the flue gas
temperature to drop, which in turn may reduce the wall temperature below the dew point causing condensation to
appear on the upper part of the chimney first. This condensation may drip back as far as the flue pipe and heat
exchanger, where corrosion may occur if not treated.
To prevent condensation, it is necessary that the internal chimney wall temperature always be kept above the dew
point. The chimney may have to be lined with a flue liner if the temperature loss is too great for the furnace. A liner
will act as an insulator and reduce the flue gas temperature loss. Insulation may be added around the liner for further
Summary of Contents for PGL20-180
Page 24: ...All installations and services must be performed by qualified service personnel 22...
Page 25: ...All installations and services must be performed by qualified service personnel 23...
Page 26: ...All installations and services must be performed by qualified service personnel 24...
Page 27: ...All installations and services must be performed by qualified service personnel 25...
Page 35: ...All installations and services must be performed by qualified service personnel 33...
Page 36: ...All installations and services must be performed by qualified service personnel 34...
Page 37: ...All installations and services must be performed by qualified service personnel 35...
Page 38: ...All installations and services must be performed by qualified service personnel 36...