background image

All installations and services must be performed by qualified service personnel.

 

 

6

Piping from the propane tank to the furnace must follow 
the recommendations of the gas supplier.  In the 
absence of local codes governing gas piping selection 
and installation, follow the National Fuel Gas Code, 
ANSI Z223.1 / NFPA 54-1999, or latest edition. 

 

A readily accessible, manual gas shutoff valve (design-
certified for the applicable gas) with a non-displaceable 
rotor member shall be installed within six (6) feet of the 
furnace. 

 

A pipe union, or flanged connection, shall be provided 
directly up stream of the burner to allow burner removal.  
Unions must be of a ground joint type or flange-jointed 
type using a gasket resistant to the corrosive effects of 
LP gases.  Pipe dope or sealant design-certified to be 
resistant to the action of the LP gases should be used on 
all threaded joints. 

 

The burner is setup to be piped to the gas supply 
through the right or left-hand side of the furnace.  For 
service purposes, it is recommended the gas union be 
located inside the furnace. 

 

A drip leg must be used on both propane and natural 
gas installations immediately upstream of the furnace in 
order to trap oil, condensate, and other impurities which 
might otherwise lodge in the gas valve, or plug the main 
burner orifice.  A drip leg shall be provided at the outlet 
of the gas meter when there is excessive condensation 
between the gas meter and the furnace.  

 

Failure to install drip leg(s) may void the manufacturer’s 
limited warranty on the furnace. 

 

For natural gas, the maximum supply pressure is 14.0 in.  
W.G. and the minimum supply pressure, for purposes of 
input adjustment, is 5.5 in.  W.G. 

 

For  propane  gas,  the  maximum supply pressure is  14.0 
in.    W.G.  and  the  minimum  supply  pressure,  for 
purposes of input adjustment, is 11.0 in.  W.G.

 

 

ELECTRICAL WIRING 

c

 CAUTION: 

When testing electrical equipment, 

always follow standard  electrical procedures and 
precautions. 

 

A Separate power supply from all other circuits is 
needed, it should be no smaller than 14 Ga., insulated 
copper wire with a temperature rating of 60ºC, or 
greater.  Install current protection and disconnect. All 
electrical wiring must be installed in strict accordance 
with local ordinances and codes. In the absence of local 
ordinances and codes, all electrical wiring must conform 
to the requirements of the National Electric Code, 
ANSI/NFPA 70- latest edition. 

 

Remove the Furnace Control Box Cover. Route the 
Power Supply Lines through the knock out in the left side 
casing with a conduit connector or proper connection. 
Connect the power supply L1 (Hot) line to the Black wire 
labeled LI. Connect the power supply L2 (Neutral) to the 
white wire labeled L2.  Connect the Power Supply 
Ground wire to the Green Wire. Secure all connections 
with the yellow wire nuts provided.  

 

Refer to the electrical diagrams contained in Appendix B 
of this manual for an electrical schematic, a connection 
diagram, and operating instructions. 

 

Room Thermostat 

A room thermostat must be connected to the Furnace 
control.  This is typically a low voltage (24 VAC) circuit. 
Consult the National Electrical Code, ANSI/NFPA 70-
2017, or latest edition for guidelines for proper wiring 
methods and materials for this circuit. The room 
thermostat should be located on an interior wall in the 
natural circulating path of the room air. 
 
The thermostat should 

not

 be installed in a location 

where it is directly exposed to, 

 

 

cold air infiltration, i.e. drafts from outside 
openings such as windows and doors,  

 

air currents produced by supply air 
registers, and 

 

heat from a nearby source, such as a 
fireplace, electrical appliances, lamps, solar 
radiation, a wall enclosing warm air ducts, a 
chimney, or a flue gas vent. 

 
Most room thermostats are equipped with an 
adjustable heat anticipator, set the thermostat 
heat anticipator to match the control current of 
the furnace as indicted on the furnace wiring 
diagram. 
  

INITIAL START UP: 

This  furnace  does  not  have  a  pilot.    It  is 
equipped  with  a  hot  surface  igniter,  which 
automatically  lights  the  burner.    Do  not  attempt 
to light the burner by hand.  Check the following 
items before the initial start-up. 
1.  Check all wiring for proper hook up.  Tighten 

any loose connections. 

2.    Using  a  soap  solution,  leak  test  gas  piping 

connections. 

3.  Check all tubing connections to the pressure 

switch,  inducer,  burner  box,  and  gas  valve 
and make sure they are connected firmly at 
all their connection points. 

4.  Check flue pipe, combustion air inlet, and all 

joints for tightness  and to  make sure there 
is no blockage. 

5.   Make sure air filter is in place. 
6.   Make sure the outside vent and  air  intakes 

are  installed  according  to  instructions  and 
are free from blockage. 

 
 

INTIAL OPERATION OF THE FURNACE: 

 

INTIAL START UP 

c

  WARNING: 

Turn  off  power  to  furnace  before  it  is 

placed  into  service.    The  gas  piping  system  must 
have  been  leak  tested  by  a  qualified  heating 
contractor.  
 

c

  WARNING: 

It  may  be  necessary  to  purge  the  air 

out  of  the  gas  line  for  initial  start-up  of  the  furnace 
after  installation.    A  qualified  heating  contractor 
should  do  this.    If  excessive  gas  escapes  when 
purging  the  gas  supply  at  the  union,  allow  the  area 
to ventilate for at least 15 minutes before attempting 
to  start  the  furnace.    Propane  gas  is  especially 
dangerous  because  the  specific  gravity  of  propane 
gas  allows  it  to  accumulate  at  floor  level  at  a 
dangerous concentration.  

Summary of Contents for GMA1-60D48N

Page 1: ...Homes Buildings PLEASE READ THESE INSTRUCTIONS PRIOR TO INSTALLATION INITIAL FIRING AND BEFORE PERFORMING ANY SERVICE OR MAINTENANCE THESE INSTRUCTIONS MUST BE LEFT WITH THE USER AND SHOULD BE RETAINE...

Page 2: ......

Page 3: ...OPERATION OF THE FURNACE 6 Initial Start Up 6 Adjustment of Heat Input 7 Burner Adjustment 8 Setting Temperature Rise 8 Furnace Check Out Procedure 8 Instructions to Our Customer End User 8 SERVICE 9...

Page 4: ...n recovering your claim against the transportation company Warranties c WARNING The manufacturer of this equipment assumes no liability for any damages resulting from unauthorized modifications made t...

Page 5: ...e Improper installation may create a fire hazard and damage internal equipment as well as void all manufacturers warranties For best performance locate the furnace so that it is centralized with respe...

Page 6: ...terials located in the return air system must have a flame spread classification of 200 or less Wiring materials located in the return air duct system must conform to Article 300 22 of the latest edit...

Page 7: ...With the gas piping pressurized all gas piping connections must be leak tested using a strong soap and water solution Any leaks must be repaired immediately after turning off the gas supply A final te...

Page 8: ...ly L1 Hot line to the Black wire labeled LI Connect the power supply L2 Neutral to the white wire labeled L2 Connect the Power Supply Ground wire to the Green Wire Secure all connections with the yell...

Page 9: ...9 2 001 3 000 30 26 2 10mm 42 3 001 4 000 30 27 45 2 30mm 4 001 5 000 1 8 28 2 00mm 43 5 001 6 000 31 29 1 95mm 2 20mm 6 001 7 000 31 29 48 2 15mm 7 001 8 000 32 30 49 45 8 001 9 000 33 1 8 50 2 00mm...

Page 10: ...connected to the Heat terminal on the integrated furnace control with one of the higher speed blower leads attached to a terminal marked Park Be sure to attach any unused blower leads to a terminal ma...

Page 11: ...ire control should be replaced as the control is not field repairable If the sensed failure is in the system external to the control the LED will flash in the following flash pause sequences to indica...

Page 12: ...s Yes No No Yes ARE WIRES CONNECTED PROPERLY No CORRECT WIRE CONNECTIONS No Yes Yes No Yes IS THE INDUCER BLOWER OPERATING Yes TROUBLESHOOTING GUIDE THE SYSTEM IS STARTED BY SETTING THE THERMOSTAT TO...

Page 13: ...ER TERMINALS IND IND N AT THE INTEGRATED CONTROL CHECK THE INTEGRATED CONTROL DIAGNOSTIC LED LAMP RESET BY INTERRUPTING POWER TO CONTROL FOR MORE THAN ONE SECOND IF LED STAYS ON CONTINUOUSLY REPLACE I...

Page 14: ...ROOF OF FLAME CHECK Yes CHECK ACROSS THE CIRCULATING AIR BLOWER TERMINALS CIR N HEAT FOR PROPER VOLTAGE REPLACE THE INTEGRATED CONTROL No No Yes DOES THE CIRCULATING AIR FAN COME ON WHEN ENERGIZED No...

Page 15: ...NS CHECK FOR SHORT IN WIRE TO THERMOSTAT AND CORRECT IF NECESSARY DOES BURNER SHUT OFF WHEN THERMOSTAT IS SATISFIED No No No Yes Yes Yes Yes Yes IS LED LIGHT ON INTEGRATED CONTROL FLASHING DOES THE CI...

Page 16: ...replaced to ensure proper venting Vent pipes should also be inspected for any signs of corrosion deterioration or leakage that may cause combustion by products to infiltrate the home or indoor enviro...

Page 17: ...g for signs of excessive heat such as discoloration of components materials damaged from rust or corrosion soot or carbon build up EXTERIOR OF FURNACES The furnace exterior should be inspected for sig...

Page 18: ...All installations and services must be performed by qualified service personnel 16 APPENDIX A REPLACEMENT PARTS GMA1 SERIES...

Page 19: ...All installations and services must be performed by qualified service personnel 17 GMA1 SERIES...

Page 20: ...All installations and services must be performed by qualified service personnel 18 GMC1 SERIES...

Page 21: ...All installations and services must be performed by qualified service personnel 19 GMC1 SERIES...

Page 22: ...All installations and services must be performed by qualified service personnel 20 GMA1 GMC1 SERIES BURNER ASEMBLY...

Page 23: ...All installations and services must be performed by qualified service personnel 21 APPENDIX B WIRING DIAGRAM REVISE...

Page 24: ...ce Motor Current Draw Amps vs External Static pressure in WC 0 1 0 2 0 3 0 4 0 5 0 6 0 7 Low 3 01 2 95 2 90 2 82 2 70 2 62 2 53 ML 4 06 3 84 3 75 3 62 3 48 3 34 3 13 MH 5 43 5 29 5 16 5 01 4 74 4 58 4...

Page 25: ...ace Motor Current Draw Amps vs External Static pressure in WC 0 1 0 2 0 3 0 4 0 5 0 6 0 7 Low 3 01 2 95 2 90 2 82 2 70 2 62 2 53 ML 4 06 3 84 3 75 3 62 3 48 3 34 3 13 MH 5 43 5 29 5 16 5 01 4 74 4 58...

Page 26: ...Current Draw Amps vs External Static pressure in WC 0 1 0 2 0 3 0 4 0 5 0 6 0 7 Low 3 04 2 93 2 88 2 79 2 72 2 64 2 53 ML 3 85 3 78 3 66 3 55 3 45 3 31 3 15 MH 5 40 5 23 5 06 4 88 4 70 4 52 4 30 High...

Page 27: ...ace Motor Current Draw Amps vs External Static pressure in WC 0 1 0 2 0 3 0 4 0 5 0 6 0 7 Low 3 04 2 93 2 88 2 79 2 72 2 64 2 53 ML 3 85 3 78 3 66 3 55 3 45 3 31 3 15 MH 5 40 5 23 5 06 4 88 4 70 4 52...

Reviews: