5.5
Cooling
COOLING is used to activate cooling function. DESIR.COOL TEMP. is the de-
sired temperature for cooling. COOL.MODE ACTIVE gives the lowest out-
door temperature with cooling operation is permitted.
Caution
Low temperatures in the system can cause
condensation on pipes and pipe connections,
which could cause moisture damage to the
building. Make sure every pipe and pipe con-
nection is properly insulated if cooling stop
temperature is set to below 16°C (default).
5.6
Reading of temperatures
OUTDOOR
ROOM
OP. DATA
CONDENSER OUT
SUPPLY LINE
CONDENSER IN
-2˚C
HEAT DEMAND
58˚C
20˚C
40(42)˚C
HOT WATER
48˚C
38.5˚C
34.3˚C
No values can be changed in this menu. The set point value for the supply
line is shown within the brackets.
The different temperatures that the installation has are shown here. All temperatures are stored back in time so
that they can also be displayed in the form of graphs.
If ROOM shows 20°C the heat curve is unaffected. If ROOM shows higher or lower, this indicates that the heat
curve has been adjusted up or down.
5.7
Reading the operating time
0H
0H
0H
0H
0H
0H
0H
COMPRESSOR
OPERAT. TIME
HEATING
COOLING
IMM. HEAT 1
IMM. HEAT 2
IMM. HEAT 3
HOT WATER
COMPRESSOR shows the total time in hours that the heat pump has been
in operation since installation. HEATING and COOLING shows the time the
heat pump has been producing heat and cooling. IMM. HEAT 1, 2 and 3 re-
fer to the immersion heater and its different power stages.
User Guide
iTec Eco
AWIE01UG102
Thermia AB
16