background image

-  - 

10

Indoor Unit Installation 

 
Install the Rear Panel (mounting plate)  
 

Always mount rear panel horizontally. 
Hold the rear panel on the wall where you want the unit to be located and ensure that it is level using a plumb line or 
level. Once leveled, mark the screw locations on the wall. 
Fasten the rear panel to the wall at the location marked using the screws supplied with the unit. 
Insure that the panel has been mounted firmly to withstand the weight of the unit, with the weight being evenly 
distributed by each screw. 
 

Install the Piping Hole 
 

 

Select the location for the piping hole - either left-positioned or right-positioned (see installation dimension 
diagram on page 5 and page 6). 

 

Make piping hole in the wall approximately 2.5 inches in diameter at a slight downward slant (this ensures proper 
drainage). 

 

Insert a piping-hole sleeve in the hole (i.e. PVC pipe) to prevent the connection piping and wiring from being 
damaged.  

 

Install Drainage Hose Extension (optional)  
 

 

Drainage hose extension is included with unit, for use if attached drainage line is not long enough for your 
application. 

 

Please note that the extension can be installed after existing drainage pipe is fed through wall later in the 
installation process, if it is determined later that it is necessary. 

 

Do not wrench or bend drainage hose or extension. 

 
Wire the Indoor Unit. 
 

 

Note: All electrical wiring must be done by a qualified technician in accordance with local electrical codes.  

 

A separate circuit breaker must be provided. 

 

AC power for the indoor unit is provided by the power cable that runs between the outdoor unit and the indoor 
unit.  

 

If a disconnect switch is required for the indoor unit, it must be properly rated. (see specifications) 

 

 

MODEL 

 

INTERCONNECTING

WIRE GAUGE 

POWER 

SUPPLY WIRE 

GAUGE 

Min  

Circuit 

Ampacity 

Max 

CIRCUIT 

BREAKER 

 

Max 

Fuse  Size 

MS29A13115A 

16 AWG 

14 AWG 

10 AMP 

15 AMP 

15 AMP 

MS212A13115A 

16 AWG 

14 AWG 

11.6 AMP 

20 AMP 

20 AMP 

MS212A13240A 

16 AWG 

14 AWG 

5.4 AMP 

15 AMP 

15 AMP 

MS218A13240A 

16 AWG 

14 AWG 

10.5 AMP 

20 AMP 

20 AMP 

 

Summary of Contents for MS212A13115A

Page 1: ...INSTALLATION INSTRUCTIONS MINI SPLIT AIR CONDITIONING SYSTEMS FOR MODELS MS29A13115A MS212A13115A MS212A13240A MS218A13240A 950 0015 REV J 12 14 06...

Page 2: ...Unit Parts and Features 3 Installation Dimension Diagram 5 Safety Warnings 7 Selection of Installation Location 8 Indoor Unit Installation 9 Outdoor Unit Installation 12 Testing 14 Warranty 17 Specif...

Page 3: ...2...

Page 4: ...SEER Indoor Unit MS212A13115EA SYSTEM MODEL MS212A13115A Outdoor Unit MS212A13115CA 12 000 BTU 115 VAC 13 SEER Indoor Unit MS212A13240EA SYSTEM MODEL MS212A13240A Outdoor Unit MS212A13240CA 12 000 BTU...

Page 5: ...4 ________________________________________________________________ Name and Function of each Part Models MS29A13115A MS212A13115A MS212A13240A...

Page 6: ...5 ________________________________________________________________ Name and Function of each Part Model MS218A13240A...

Page 7: ...6 ________________________________________________________________ Installation Dimension Diagram Models MS29A13115A MS212A13115A MS212A13240A...

Page 8: ...7 ________________________________________________________________ Installation Dimension Diagram Model MS218A13240A...

Page 9: ...not use excessive torque on flare nuts during connection of the refrigeration tubes or service valve on discharge line may be damaged Do not install indoor unit in damp or wet locations Electrical ins...

Page 10: ...hting and away from any excessive heat source steam or flammable materials Outdoor Unit Allow sufficient ventilation around the unit see installation dimension diagram page 5 and page 6 The air intake...

Page 11: ...m being damaged Install Drainage Hose Extension optional Drainage hose extension is included with unit for use if attached drainage line is not long enough for your application Please note that the ex...

Page 12: ...Lines Refrigeration Lines and wiring can be routed from the indoor unit several different ways using the cut out access pieces on the back of the unit Bend the refrigeration lines carefully to the po...

Page 13: ...te leave remainder unwrapped to allow for remaining step in installation of the outdoor unit and connecting the indoor unit to the outdoor unit Carefully push bundled lines through the piping hole Han...

Page 14: ...sure that they do not sweat This will help to maintain the unit at its proper capacities Once all lines have been properly insulated bundle the refrigeration lines with the wiring conduit and wrap sec...

Page 15: ...ion using proper hardware 5 Connect refrigeration lines to Outdoor Unit Remove caps on outdoor unit Use standard A C practices to attach the refrigeration lines bundled in step 2 to the outdoor unit T...

Page 16: ...unit Tighten bonnet cover of gas valve and open gas and liquid valves completely 4 System Testing Before testing the system ensure that cut off valves of the connection pipes are opened and that all d...

Page 17: ...oor and outdoor unit Verify that unit has been connected as the proper wiring indicates Press ON OFF button on remote Press MODE button to verify operation of all functions Unit may take up to 4 min t...

Page 18: ...Turn unit to Cool mode Allow 3 4 min for compressor timer to operate Check for line voltage between pins 1 and 2 of indoor unit If no voltage is present please call technical support The unit vibrates...

Page 19: ...tion either repair or replace the unit free of charge within a reasonable time after the unit is returned This warranty DOES NOT cover z Damage accidental or otherwise to the unit while in possession...

Page 20: ...el Panasonic 2P14S126B1Y Panasonic 2P16S126B1P Panasonic 2P15S236A1H Hitachi SL253SN C7EU Compressor Type Rotary Rotary Rotary Hermetic motor compressor L R A A 49 54 26 39 Compressor RLA A 7 5 8 8 4...

Page 21: ...pen short 4 6 sec Pause before Flash Sequence F5 Outdoor sensor open short 5 F6 Cooling Overload 6 F7 Unused 7 F8 Current Overload 8 F9 Unused 9 F0 Unused 10 H1 Defrost 1 H2 Static duct clean protect...

Reviews: