NOTE: After installation, the pressure reading should be as indicated below. Take from the service port, the
pressure under the outdoor temperature should match the charts readings.
Cooling chart:
COOLING MODE
Outdoor Temp >
Indoor Temp v
75°F
85°F
95°F
105°F
115°F
70°F
119.0
113.0
117.0
125.0
147.0
PSI
75°F
124.0
120.0
126.0
132.0
155.0
PSI
80°F
135.0
129.0
132.0
140.0
162.0
PSI
Pressure (PSI)
Outdoor Temperature
It is recommended to record and charge when the outdoor temperature is within the chart temperatures.