background image

950-0211revA                                                                              - 10 -                                                                                   March 7, 2014 

 

 

Installation (CONT’D). 

If a flared section is defective, cut it off and follow standard flaring procedures again.

  

 

See caution note page 5. 
Align the center of the piping flare to its’ mating connector, then screw on the 
flare nut by hand and then tighten the nut with a spanner and torque wrench.

  

 

Note

: Exceeding the tightening torque will damage the flare surface. 

 
 

 

 

 

 

Step 9 

Evacuation 
Gauges can now be attached to the service port - 
SERVICE PORTS HAVE A 1/4

” CONNECTION TO 

GAUGES.  
Use caution to ensure that the proper size fittings are 
used when connecting.  
Once the gauges are attached the line set can be leak 
checked using nitrogen at 300 PSIG. Evacuate the unit 
down to a minimum of 500 Microns, break vacuum with nitrogen to further leak check.  
Re-evacuate the system down to 500 Microns or lower. This is an R410A system, it is essential that a deep 
vacuum be pulled on the system to remove all traces of moisture. (See page 23 for The Importance of a Deep 
Vacuum).

 

 
Step 10 

 

DANGER  

MAIN POWER WIRING: ELECTRICAL WIRING SHOULD BE DONE BY A LICENSED ELECTRICIAN IN 
ACCORDANCE WITH NATIONAL AND LOCAL CODES. 
 

 

 

Tip: Small electrical screwdriver is required for unit terminals. Breaker size and wiring must be sized for 

the rating plate amperage. If a smaller than required breaker is used there is a possibility of unit damage. Use 
breaker as specified in Specifications Table page 15 to page 19. 

 

Each system installed must have a separate branch circuit with an individual breaker/fuse. A local disconnect 
should be installed adjacent to the outdoor unit in accordance with National and Local Electrical Codes. The 
outdoor unit provides power for the indoor unit therefore, no disconnect is required between the outdoor and 
indoor units.  

 

Line voltage from the disconnect should be wired to: 
N - L 

– Ground screw  (115V Unit)  

L1 - L2 

– Ground screw  (208/230V Unit).  

Remove right side knockout on the terminal access panel for whip/wiring connection. Ground connection must 
be made to the terminal plate. 

 

 

 

Tip: For easier access to the terminals in the outdoor unit remove the lower access panel to install whip 

and Seal Tite connectors for conduit. 

 
Step 11  
CONTROLS WIRING 
USE A MINIMUM 16 AWG WIRE.  

Remove terminal covers from Indoor unit and wire to the terminals. A small electrical screwdriver required. 
Control wiring from the outdoor unit must be a point to point; i.e. the terminal that the wire is attached to on the 
outdoor unit must be the same terminal it is wired to in on the Indoor unit.                        

*** 

DO NOT CROSS WIRES BETWEEN TERMINALS. ***

 

THIS IS EXTREMELY IMPORTANT!

  

Miswiring (cross connecting wires) between the indoor unit and outdoor unit will cause the unit to fail to operate 
at a minimum, and can seriously damage the unit in the worst case. Use extreme care to ensure that wiring 
between the inside unit and the outside unit is per the wiring diagrams on the next pages.  
Ground wires connected to the terminal plate indoor and outdoor units must be grounded.

  

Tightening Torque Table 

1/4

” 

11-15 

Ft-lbs 

3/8

” 

25-30 

Ft-lbs 

1/2

” 

36-42

” 

Ft-lbs 

5/8

” 

54-58 
Ft-lbs 

 

 

 

Summary of Contents for 12A45YIMI

Page 1: ...Inc MINI SPLIT INSTALLATION AND MAINTENANCE MANUAL A C HEAT PUMP 9A45YIMI 9H45YIMI 12A45YIMI 12H45YIMI 12A45ZIMI 12H45ZIMI 18A45ZIMI 18H45ZIMI 24A45ZIMI 24H45ZIMI 9A45YOMI 9H45YOMI 12A45YOMI 12H45YOM...

Page 2: ...Items for Considerations 3 Unit Installation 5 Unit Installation indoor 6 Unit Installation outdoor 9 Main Power Wiring 10 Controls Wiring 10 Wiring Diagram 11 Unit Start Up 13 Refrigerant Charge 14...

Page 3: ...m voltage before installing the unit installing and operating a unit with the incorrect voltage may result in malfunction or other issues and will void the warranty 2 Units must be connected to a corr...

Page 4: ...lation parameters The below data is for the Northeast section of the US Increase capacity by 25 for the East 30 for the South and 40 for the West Computer or Data Server Rooms These require ballpark s...

Page 5: ...d for the new refrigerant R410A units For connecting pipes use new and clean piping materials with high pressure fittings made for R410A only The best and recommended solution is not to use the existi...

Page 6: ...door unit closer to the indoor unit and also for a convenient installation We offer wall brackets Our Catalog BR 440L for up to 440 lbs as an accessory UNIT INSTALLATION CAUTION Follow Instructions fa...

Page 7: ...nit must be located a minimum of 4 ft from the floor and 6 from the ceiling Choose an area where the wall is plumb and determine how to best run the unit interconnects ALL VIEWED FROM FRONT SIDE L R H...

Page 8: ...n the left and right sides of the unit to route the piping and wiring connections Drill a 3 diameter hole through the wall for line set If using the installation kit measure the diameter of the sleeve...

Page 9: ...d the 16 AWG interconnect wiring between indoor and outdoor maximum of wires required is 4 through the unit electrical connection if required by local codes an electrical connector can be attached to...

Page 10: ...le may be required Ensure location does not impede access around unit and pose a disturbance to neighboring areas Step 8 Refrigerant Line Set Piping Interconnecting line set between the outdoor unit a...

Page 11: ...alled must have a separate branch circuit with an individual breaker fuse A local disconnect should be installed adjacent to the outdoor unit in accordance with National and Local Electrical Codes The...

Page 12: ...L1 L2 S L1 L2 S L1 L2 L1 L2 S L1 L2 S L1 L2 24K 230VAC Green wire for GND Green wire for GND Green wire for GND Note 1 When connecting terminals wire color is not important except green which should a...

Page 13: ...ilding codes Remember water only flows downhill to ensure positive draining from the unit Check using water for a positive flow of condensate Route the condensate hose on the bottom of the bundle maki...

Page 14: ...tems Remove brass caps from the service valves Open the SUCTION line valve first to prevent any possibility of oil clogged in the capillary tube This can occur if the liquid line valve is opened first...

Page 15: ...7 25 oz 8 86 oz 12A45YMI 12H45YMI 0 161 oz 0 81 oz 1 61 oz 3 22 oz 4 03 oz 5 64 oz 7 25 oz 8 86 oz 12A45ZMI 12H45ZMI 0 161 oz 0 81 oz 1 61 oz 3 22 oz 4 03 oz 5 64 oz 7 25 oz 8 86 oz 18A45ZMI 18H45ZMI...

Page 16: ...ure should match the charts readings Cooling chart COOLING MODE Outdoor Temp Indoor Temp v 75 F 85 F 95 F 105 F 115 F 70 F 119 0 113 0 117 0 125 0 147 0 PSI 75 F 124 0 120 0 126 0 132 0 155 0 PSI 80 F...

Page 17: ...p v 57 F 47 F 37 F 27 F 17 F 55 F 439 0 413 0 367 0 330 0 302 0 PSI 65 F 471 0 435 0 386 0 368 0 339 0 PSI 75 F 489 0 457 0 403 0 381 0 362 0 PSI Pressure PSI Outdoor Temperature It is recommended to...

Page 18: ...uF 3 0 3 0 Speed H M L RPM 1200 1050 800 1200 1050 850 Indoor air flow H M L CFM 480 420 320 480 420 320 Indoor noise level H M L dB A 39 35 28 39 35 28 Indoor unit Dimension W D H IN 26 77x7 01x10 04...

Page 19: ...apacitor uF 3 0 3 0 Speed H M L RPM 1200 1050 800 1200 1050 800 Indoor air flow H M L CFM 580 500 400 580 500 400 Indoor noise level H M L dB A 39 35 29 39 35 29 Indoor unit Dimension W D H IN 30 31X7...

Page 20: ...ut W 43 43 Capacitor uF 1 5 1 5 Speed H M L RPM 1200 1050 800 1200 1050 800 Indoor air flow H M L CFM 600 530 400 600 530 400 Indoor noise level H M L dB A 39 35 31 39 35 31 Indoor unit Dimension W D...

Page 21: ...5 Capacitor uF 1 5 1 5 Speed H M L RPM 1250 1100 800 1250 1100 800 Indoor air flow H M L CFM 750 660 480 750 660 480 Indoor noise level H M L dB A 42 39 31 42 39 31 Indoor unit Dimension W D H IN 35 6...

Page 22: ...W 80 5 80 5 Capacitor uF 3 0 3 0 Speed H M L RPM 1200 1100 900 1200 1100 900 Indoor air flow H M L CFM 1250 1150 950 1250 1150 950 Indoor noise level H M L dB A 47 45 39 49 45 39 Indoor unit Dimensio...

Page 23: ...ace outdoor temperature sensor and or replace indoor PCB F2 Condenser coil temperature sensor T3 open circuit or short circuit Replace condenser coil temperature sensor and or replace indoor PCB F3 Co...

Page 24: ...line in a fine mist with ice crystals forming at the point of expansion Freeze up is not the only problem caused by moisture It can also result in corrosion the effects of which are not apparent until...

Page 25: ...a reasonable time after the unit is returned This warranty does not cover Damage accidental or otherwise to the unit while in possession of the consumer that is not a result of a defect in material in...

Reviews: