EVCA Modulating Fire Test Procedures and Specifications
APPENDIX D (Cont…) - TSBC
TM
SETUP Menu
Display
Factory
Settings
Range
Description
Low
Fire
Hold
20
10 to 1200 (s)
Time modulation rate is held at present value (Low Fire Spd or Fan Purge Spd
depending on the state and configuration of spare input) after the Fuel Valve
Energized Input (CS) is energized.
Post
Purge
Time
30
0 to 600 (s)
Time modulation rate is held at Fan Purge Spd after the Fuel Valve Energize Input
(CS) is de-energized.
Local
Pid
P
20
0 to 10000
Proportional Gain value for boiler outlet temperature sensor control Modes. A larger
gain value results in tighter, more active, PID control. Gain is the primary PID
modulation rate tuning adjustment and provides the immediate modulation rate
response.
Local
PID
I
30
0 to 10000
Integral gain value for boiler outlet temperature sensor control Modes. A smaller
value makes the Integral ramp in less time (i.e., faster). Integral is a secondary PID
modulation rate tuning adjustment that ramps the output over time (typically
minutes).
Local
PID
D
0
0 to 10000
The Derivative gain value for boiler outlet temperature sensor control Modes. A
larger Derivative gain value produces a larger PID output contribution proportional to
the rate of change of the error (Setpoint – Boiler Outlet Temperature). When set
equal to zero it has no effect on the output.
Remote
PID
P
20
0 to 10000
Proportional Gain value for Remote System Temperature sensor control Modes.
Refer to Local PID P for explanation.
Remote
PID
I
30
0 to 10000
Integral Gain Term for Remote System Temperature sensor control Modes. Refer to
Local PID I for explanation.
Remote
PID
D
0
0 to 10000
Derivative Gain Term for Remote System Temperature sensor control Modes. Refer
to Local PID D for explanation.
Mixing
Valve
P
10
0 to 10000
Proportional Gain value for boiler Inlet temperature sensor control mode. A larger
gain value results in tighter, more active, PID control. Gain is the primary PID
modulation rate tuning adjustment and provides the immediate mixing valve
modulation response.
Only visible when mixing valve = yes.
Mixing
Valve
I
60
0 to 10000
Integral gain value for boiler inlet temperature sensor control mode. A smaller value
makes the Integral ramp in less time (i.e., faster). Integral is a secondary PID
modulation rate tuning adjustment that ramps the output over time (typically
minutes).
Only visible when mixing valve = yes.
Mixing
Valve D
0
0 to 10000
The Derivative gain value for boiler inlet temperature sensor control mode. A larger
Derivative gain value produces a larger PID output contribution proportional to the
rate of change of the error (Setpoint – Boiler Inlet Temperature). When set equal to
zero it has no effect on the output.
Only visible when mixing valve = yes.
Max
Delta T
P
10
0 to 10000
Proportional Gain value for boiler differential (boiler outlet minus inlet temperature
sensor) temperature control mode. Refer to Local PID P for explanation.
Only visible when mixing valve = yes.
Max
Delta T
I
60
0 to 10000
Integral Gain value for boiler differential (boiler outlet minus inlet temperature
sensor) temperature control mode. Refer to Local PID I for explanation.
Only visible when mixing valve = yes.
Max
Delta T
D
0
0 to 10000
Derivative Gain Term for boiler differential (boiler outlet minus inlet temperature
sensor) temperature control mode. Refer to Local PID D for explanation.
Only visible when mixing valve = yes.
Page 16 of 22
D.
SETUP MENU
(continued)
Summary of Contents for EVS SERIES
Page 14: ...14 Figure 4 Vertical Pressurized Venting ...
Page 16: ...16 Figure 5 Typical Negative Pressure Conventional Venting ...
Page 18: ...18 Figure 7 Vertical Air Intake Piping ...
Page 27: ...27 Figure 9a 208 230 460V 1 3 ph 60 Hz Supply Power Wiring Schematic ...
Page 28: ...28 Figure 9b 120V 1ph 60Hz Supply Power Wiring Schematic ...
Page 29: ...29 Figure 9c Standard UL FM CSD 1 Wiring Diagram EVS 500 2000 ...
Page 31: ...31 Figure 9e Standard UL FM CSD 1 EVS 2000S 3000 ...
Page 35: ...35 Figure 11 Modular System Horizontal Air Intake Piping ...
Page 36: ...36 Figure 12 Modular System Vertical Air Intake Piping ...
Page 37: ...37 Figure 13 Modular System Typical One Pipe Water Piping ...
Page 38: ...38 Figure 14 Modular System Typical Primary Secondary Water Piping ...
Page 39: ...39 Figure 15 Modular System Typical Primary Secondary without System Pump ...
Page 40: ...40 Figure 16 Modular System Typical Reverse Return Water Piping ...
Page 41: ...41 Figure 17 Modular System Reverse Return with System Pump Only ...
Page 42: ...42 Figure 18 Modular System Typical Primary Secondary with Reverse Return ...
Page 58: ...58 Figure 19 Combustion Chamber Assembly ...
Page 60: ...60 Figure 20 Burner Assembly FRONT VIEW TOP VIEW ...
Page 62: ...62 Figure 21 UL FM CSD 1 Main Gas Train Assembly ...
Page 65: ...65 Figure 22b DB B Gas Train 500 750 Figure 22c DB B Gas Train 1000 2000 ...
Page 70: ...70 Figure 23 Jacket Panels ...
Page 74: ...74 Figure 25 Pilot Assembly Bishop Design ...
Page 88: ...88 NOTES ...
Page 89: ...89 NOTES ...
Page 90: ...90 NOTES ...
Page 91: ...91 NOTES ...