TSBC Instruction Manual
Page 46 of 48
Appendix A
Parameter Summary (continued)
Network
Relevant*
Parameter
Range/Choices
Security
Level**
Page
Setup Menu (continued)
-
Blower Spd High
0 to100 % of full scale
Factory
31
-
Blower Spd Low
0 to100 % of full scale
Factory
31
-
Low Fire Spd
0 to100 % Modulation Rate
Factory
31
-
Fan Purge Spd
0 to100 % Modulation Rate
Factory
31
Yes
Low Fire Hold
0 to 1200 sec
Factory
31
Yes
Post Purge Time
0 to 600 sec
Factory
31
Yes
Local PID P
0-10000
Supervisor 33
Yes
Local PID I
0-10000
Supervisor 33
Yes
Local PID D
0-10000
Supervisor 33
Yes
Remote PID P
0-10000
Supervisor 33
Yes
Remote PID I
0-10000
Supervisor 33
Yes
Remote PID D
0-10000
Supervisor 33
Yes
Mixing Valve P
0-10000
Supervisor 34
Yes
Mixing Valve I
0-10000
Supervisor 34
Yes
Mixing Valve D
0-10000
Supervisor 34
Yes
Max Delta T P
0-10000
Supervisor 34
Yes
Max Delta T I
0-10000
Supervisor 34
Yes
Max Delta T D
0-10000
Supervisor 34
Setpoint Menu
Yes
Operational Setpoint
60 F to 230 F
Basic
19
Yes
On point
0 F to – 99 F
Basic
19
Yes
Off Point
0 F to 99 F
Basic
19
Yes
High Temp Stop
60 F to 230 F
Basic
19
Yes
DHWP setpoint
140 F to 230 F
Basic
19
Yes
WWSD setpoint
40 F 90 F
Basic
19
Yes
Max SP
140 F to 230 F
Supervisor 19
Yes
Min SP
60 F to 230 F
Supervisor 19
Yes
Min BIT
110 F to 235 F
Factory
19
Update Min Inlet H2O Temp
110 F to 180 F
Supervisor 19
Update Max H2O Delta T
20F to 50 F
Supervisor 19
Update Max Delta T Hold
20F to 50 F
Supervisor 19
Communication Menu
-
Protocol
Peer to Peer / Modbus
Supervisor 24
- Modbus
Address
1-247
Supervisor 24
-
Baud Rate
9.6 / 19.2 / 38.4
Supervisor 24
-
Parity
Odd / Even / None
Supervisor 24
-
Timeout
1 Second to 120 Seconds
Supervisor 24
-
Boiler Address
1 to 8
Supervisor 24
Parameters identified by “
Yes
” under the “
Network Relevant
” column must be configured identically on all boilers.
Unexpected boiler behavior may result if these parameter values differ among boilers on the network.
Once
communications is established between all boilers in a system, changes to parameters identified as “Yes” or
“Update” under the “Network Relevant” column at the keypad of any boiler will update that parameter in all boilers.
** To change your current security level, refer to page 42 Security Level operations.