APPENDIX
APPENDIX 1: INPUT WIRING REQUIREMENTS
Input
P ow er Input
Cur r ent
S uggested S izes (S ee Notes)
V oltage
Fr eq.
1-P h
3-P h
1-P h
3-P h
Fuse (Amps)
W ire (AW G )
W ire (Canada)
(V olts)
(Hz)
(kV A)
(kV A)
(Amps) (Amps)
1-P h
3-P h
1-P h
3-P h
1-P h
3-P h
208
50/60
12.5
11.2
60
31.1
70
40
4
8
4
8
230
50/60
12.5
11.3
54.1
28.3
70
35
4
8
4
8
240
50/60
12.6
11.4
52.3
27.5
60
35
6
8
6
8
380
50/60
13.9
12.4
36.5
18.9
45
25
8
10
8
10
415
50/60
13.9
12.6
33.4
17.5
40
25
8
12
8
12
460
50/60
13.9
12.7
30.1
16
35
25
8
12
8
12
575
Requires Transform er M odule
Line V oltages with S uggested Circuit P rotection and W ire S izes
B ased on National Electric Code and Canadia n Electrical Code
NOTES
Refer to Local and National Codes or local authority having jurisdiction for proper wiring requirements.
Cable size is de-rated based on the Duty Cycle of the equipment.
The suggested sizes are based on flexible power cable with power plug installations. For hard-wired installations
refer to local or national codes.
Cable conductor temperature used is 167° F (75° C).
An energy limiting fuse UL Class RK-1 (examples: BUSS LPS/LPN-RK or Gould-Shawmut AZK-A6K) should be
used to minimize damage to Plasma Cutting, Welding or power distribution equipment.
NEVER
use replaceable element fuses like UL Class H, or "one-time" fuses like UL Class K5.
Flexible cable must have an outside diameter of 0.69 inches (17.5 mm) or greater.
Summary of Contents for Pak Master 75XL Plus
Page 2: ......
Page 6: ......
Page 16: ...INTRODUCTION 2 2 Manual 0 2747...
Page 49: ...Manual 0 2747 6 5 REPLACEMENT PARTS This page left blank...
Page 71: ...Manual 0 2747 A 15 APPENDIX Notes...
Page 72: ...APPENDIX A 16 Manual 0 2747 APPENDIX 12 SYSTEM SCHEMATIC A 02503...
Page 73: ...Manual 0 2747 A 17 APPENDIX A 02503...
Page 74: ......