Thermal Care Aquatherm RQE Operation, Installation, And Maintenance Manual Download Page 17

13 

Fill Water Chemistry Requirements 

Water Characteristic 

Quality Limitation 

Alkalinity  (HCO

3

-

70-300 ppm 

Aluminum (Al) 

Less than 0.2 ppm 

Ammonium (NH

3

Less than 2 ppm 

Chlorides (Cl

-

Less than 300 ppm 

Electrical Conductivity 

10-500µS/cm 

Free (aggressive) Carbon Dioxide (CO

2

)† 

Less than 5 ppm 

Free Chlorine(Cl

2

Less than 1 PPM 

HCO

3

-

/SO

4

2-

 

Greater than 1.0 

Hydrogen Sulfide (H

2

S) 

Less than 0.05 ppm 

Iron (Fe) 

Less than 0.2 ppm 

Manganese (Mn) 

Less than 0.1 ppm 

Nitrate (NO

3

Less than 100 ppm 

pH 

7.5-9.0 

Sulfate (SO

4

2-

Less than 70 ppm 

Total Hardness (dH)k 

4.0-8.5 

† Dissolved carbon dioxide calculation is from the pH and total 
alkalinity values shown below or measured on the site using a test 
kit. Dissolved Carbon Dioxide, PPM = TA x 2

[(6.3-pH)/0.3]

 where TA = 

Total Alkalinity, PPM as CaCO

 

 

CAUTION: When your application requires the use of 
glycol, use industrial grade glycol specifically 
designed for heat transfer systems and equipment. 
Never use glycol designed for automotive 
applications. Automotive glycols typically have 
additives engineered to benefit the materials and 
conditions found in an automotive engine; however, 
these additives can gel and foul heat exchange 
surfaces and result in loss of performance or even 
failure of the chiller. In addition, these additives can 
react with the materials of the pump shaft seals 
resulting in leaks or premature pump failures. 

 

 

WARNING: Ethylene Glycol is flammable at higher 
temperatures in a vapor state. Carefully handle this 
material and keep away from open flames or other 
possible ignition sources. 

 

Step 3 – Initial Unit Operation 

Enter the set point temperature. Refer to the Control 
Panel Operation section for further information. 
 
Changing the set point temperature requires the unit 
display shows the Home Screen. Once the Home 
Screen shows, press the run soft key (the   under 
the “Run” box on the screen). Pressing the run 
button enables the microprocessor control functions, 
initiates an auto-vent sequence, and turns on the 
Run indicating light, which is amber when the unit is 
running. 

The vent sequence removes air that may have 
separated out from the water or been entrapped in 
the water circuit for some reason. Air in the system 
can lead to improper operation and premature 
heater failure. When initiated, the auto-vent 
sequence opens the cooling valve for the first half of 
the sequence (30 seconds is the default value for 
this) to allow the majority of the air to escape from 
the system. During this part of the sequence, “VALVE 
VENT” shows on the display. 
 
For further air purging, the vent sequence energizes 
the pump for the second half of the auto-vent 
sequence (30 seconds is the default value for this) 
while the cooling valve is open to remove any 
remaining air from the system. During this part of 
the sequence, “VALVE/PUMP VENT” shows on the 
display. 
 
Once the vent sequence is complete, the cooling 
valve is closed, the pump remains energized, and 
normal operation initiates. 
 
Check the rotation of the pump by visually 
confirming the motor shaft rotation matches the 
directional arrow sticker on the motor case. If the 
pump is running backwards, switch two of the main 
power leads, after shutting off the disconnect switch. 
 
The unit is now ready for service. 
 

Summary of Contents for Aquatherm RQE

Page 1: ......

Page 2: ......

Page 3: ...Decrease Button 4 Changing Setpoint Temperature 4 Changing Temperature Units 4 Changing Temperature Displayed 4 Using Mold Purge Option 4 Changing User Parameters 5 USB Port 5 Table 1 User Parameters...

Page 4: ...Page Intentionally Blank...

Page 5: ...ng General Mandatory Action Wear Eye Protection Wear Protective Gloves Wear Ear Protection Disconnect Before Carrying Out Maintenance or Repair Connect an Earth Terminal to Ground Only qualified perso...

Page 6: ...ols or any other major component torn loose from its mounting point Record any signs of concealed damage and file a shipping damage claim immediately with the shipping company Most carriers require co...

Page 7: ...his exceeds the maximum allowable of 2 There is a terminal block for main power connection to the main power source The main power source should be connected to the terminal block through an appropria...

Page 8: ...er button to enter the new set point temperature Changing Temperature Units The temperature unit in use shows in the display as F or C following the set point temperature The default temperature unit...

Page 9: ...press the soft key button to save the new selection Press the exit soft key the button under the Exit box on the screen to return to the home screen USB Port The USB port located on the front of the c...

Page 10: ...ssist in deaeration No loop temperature regulation occurs in this state Increase this value if you have an excessively long fluid loop Vent Bypass 120 F 32 to 260 If the process loop is above this tem...

Page 11: ...whether or not mold purge is installed as an option Setpoint Max 250 F 40 to 250 Maximum permitted machine setpoint Setpoint Min 40 F 40 to 250 Minimum permitted machine setpoint Cool Heat Rto 1 25 0...

Page 12: ...y menu according to the installed TCU options Note The unit will not operate properly if the Factory Parameters are incorrectly changed or modified For that reason these parameters can only be changed...

Page 13: ...ning to OFF is considered an operation 9 18 Cooling Water Cooling Water Temperature The cooling water temperature as measured at the end of the valve vent during normal TCU startup Value is saved thro...

Page 14: ...ts remained open when the coil was energized 15 18 Low Pres Time Low Pressure Shutdown Alarms Number of times the running TCU has remained in a low pressure paused state for so long that it created an...

Page 15: ...ference between the process value and the setpoint The goal of the control loop is to reduce this to 0 during operation Start up Every unit is factory set to deliver water in accordance with the stand...

Page 16: ...help regulate the pressure to ensure it does not exceed the pressure rating of the pressure relief valve For further assistance in installing a pressure regulating valve please contact our Customer S...

Page 17: ...es or other possible ignition sources Step 3 Initial Unit Operation Enter the set point temperature Refer to the Control Panel Operation section for further information Changing the set point temperat...

Page 18: ...t there may be a problem with the unit If this is the case refer to the Troubleshooting section of this manual or contact our Customer Service Department 2 Check the pump discharge pressure Investigat...

Page 19: ...upply is of sufficient temperature volume and pressure for the unit Drain cooling water return line is not sufficient Check the drain cooling water return line to ensure there is no restriction preven...

Page 20: ...16 Notes...

Page 21: ...17 Notes...

Page 22: ...18 Notes...

Page 23: ......

Page 24: ...es Customer Service Parts Department 847 966 2260 info thermalcare com 847 966 2260 847 966 9358 fax 847 966 2636 847 966 8560 847 966 9358 fax www thermalcare com info thermalcare com service thermal...

Reviews: