27
14.
TYPICAL PROCESS CONNECTIONS
15.
POWER REQUIRED TO START MOTOR
1.
Motor start code.
2.
Running amperage.
3.
Motor HP.
4.
Motor voltage.
kVA/HPxHPx1000
EXAMPLE : Calculate the starting amperage required for a 230 V, 2.7 HP motor with a motor start code of 8 for
compressor.
Volts = 230 HP = 2.7 Using table, Code for compressor result in kVA/HP = 8
8x2.7x1000
230
AC MOTOR
VOLT
230
AMPS
2,5
COMPRESSOR HZ
60
HP 2.7
PHASE
1
MOTOR START CODE
VENTILATOR
COMPRESSOR
kVA/HP
4
8
VOLTS
= STARTING AMPERAGE
=
93.9 A Starting the motor requires 93.9 amperes
ref. T300KT2.DWG
ref. TA500D13.TIF