THERMAL INNOVATIONS (UK) LTD | THERMAFLOW® ELECTRIC COMBINATION BOILER |
Tel: 0870 850 5207
4
0.1
Instructions general
A pressure reducing valve must be fitted to the cold water inlet if the incoming water pressure
exceeds 400 KPA (4.0 Bar).
The primary operating pressure initial charge is 120 KPA (1.2Bar) this will increase to around 200
KPA (2.0Bar) when the system has reached maximum temperature and will depend on system
volume.
The primary expansion vessel pre-charge pressure is 150 KPA (1.5 Bar) and has volume of 25 and
35 litres depending on the model of boiler.
The secondary expansion vessel pre-charge pressure is 350 KPA (1.0 Bar) and has a volume of
1litre.
The primary pressure relief valve is set to 300 KPA (3.0 Bar).
Thermaflow Model Number
TSL9/140U & TSL12/140U
TSL9/170U & TSL12/170U
Primary storage
capacity
140 litres
170 Litres
Weight when
Empty
50KG 56KG
Weight when Full
190KG 226KG
WARNING: BEFORE OBTAINING ACCESS TO TERMINALS, ALL SUPPLY CIRCUITS
MUST BE DISCONNECTED.
The
TSL9/14OU,
TSL9/170U
all have 3 heating elements fitted. Size 8” in length and are
manufactured of incaloy EN60335.2.73.
The rated power input of the appliance is ~230- 240V, 50Hz, 8,250-9,000w
The
TSL12/140U, TSL12/170U
all have 4 heating elements fitted. Size 8” in length and are
manufactured of Incaloy EN60335.2.73.
The rated power input of the appliance is ~230-240V, 50Hz, 11,000-12,000w
The elements fitted to the Thermaflow should
NOT be replaced with elements which have no
thermal cut outs
.
It is recommended that the Thermaflow has a safety and maintenance check on an annual
basis.
A pressure reducing valve must be fitted to the cold water inlet of the appliance if the
incoming pressure exceeds 400kPA (4 Bar).
The position of the Tundish (IF REQUIRED) shall be visible to the occupants and shall be
positioned away from any electrical devices.
The position of discharge pipes, (Tundish), drain valves and motorised valves etc, must be
positioned away from electrical components.
The water may drip from the discharge pipe of the pressure-relief device and must be left
open to the atmosphere.
The pressure relief device must be operated regularly to remove lime deposits and to verify
that it is not blocked.
The discharge pipe connected to the pressure-relief device must be installed in a
continuously downward direction and in a frost free environment.
(Additional Information given in G3 of the building regulations for discharge pipes)