Trapzilla

®

 Grease Interceptor

Installation and Operations Manual

TZ-1826 Models

AEF

MNL-TZ-1826  6

3. Plumbing Installation

3.1  Plumbing Considerations Prior to Installation

3.1.1  Locating the Unit

The system should be visible and easily accessible for maintenance and inspection.  Options are available 

to install the Trapzilla in a basement, suspended from a ceiling or in-ground in an exterior location.  Make 

sure adequate room is provided around the unit to allow easy access for a pump truck operator.  Make 

sure the height above the Trapzilla access cover is enough to properly service the system.

3.1.2  Inlet/Outlet Piping

The inlet and outlet piping connections require flexible sleeve pipe couplings.  Keep outlet piping as 

straight as possible.  Thermaco, Inc. recommends installation of Two-Way Cleanouts on both the Inlet and 

Outlet of Trapzilla

 

Interceptors and Solids Separators in accordance with all applicable laws, regulations 

and codes.  

These cleanouts should match the size of the Inlet and Outlet Piping (i.e. for 4” Inlet/

Outlet piping, a 4” cleanout should be used). 

Use only “sweep” connections.  Do not reduce the pipe 

sizing on the outlet piping.  Do not install “P” trap on outlet connection of system.  (Note: The system 

already has a internal gas trap)

3.1.3  Flow Controls

Trapzilla systems are supplied with a Low-Head Flow Control module (LHFC).  This should be connected 

to the inlet of the Trapzilla unit in situations where flow rate needs to be restricted to the ASME rated 

flow or when vented flow control is required by local code.

3.1.4  Venting the Outlet

An outlet vent or approved air admittance valve of at least 1/2 the diameter of the system’s outlet 

connection must be present as close as possible to the Trapzilla outlet to prevent possible siphonage 

problems.  The Vent on the Outlet piping is to be installed in accordance with all applicable laws, 

regulations and codes.  Failure to provide a vent for the system voids Thermaco’s Limited Warranty for 

the system.

3.1.5  High Head Height Applications Over Six (6) Feet (1.95 m)

For installations where there is head height of greater than 6 feet (1.95 meters), Thermaco, Inc. 

recommends installation of a code-approved Vented Flow Control Assembly (Thermaco VFCA not 

included with Trapzilla).

Note: Drawing for reference only.  Equipment must be installed in compliance with all applicable laws, regulations 

and codes, including plumbing codes.  Installation should be performed by a qualified plumber. 

3.2 Vessel Vent Connection

Venting of the Trapzilla tank is recommended by the manufacturer and required for in-door installations.  
• Vent the tank through the provided 2” NPT threaded connector on the side of the tank (This vent may 

be located above the outlet or on the side of the tank depending on model). 
• Remove and discard the plug and connect appropriate vent lines as indicated below (for 2” vent 

connection, use 2” pipe).

1

1

2

2

3

3

4

4

A

A

B

B

C

C

D

D



THIS DRAWING CONTAINS PROPRIETARY AND PATENTED MATERIAL.  THIS DRAWING MAY NOT BE REPRODUCED IN WHOLE OR PART WITHOUT

WRITTEN CONSENT FROM THERMACO, INC.  POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE.

POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREEMENT BETWEEN THERMACO, INC. AND THE HOLDER OF

THIS DRAWING.  DO NOT DESTROY THIS DRAWING, IT IS THE SOLE PROPERTY OF THERMACO, INC. AND MUST BE RETURNED UPON REQUEST.

MATERIAL (UNLESS NOTED)

FINISH (UNLESS NOTED)

646 GREENSBORO STREET

PO BOX 2548, ASHEBORO, NC 27203

VOICE 336-629-4651 FAX 336-626-5739

Decimals

.XX +/- .03

.XXX +/- .015

Unless otherwise specified

Dimensions are in inches

Tolerances

Angular

+/- 1°

CHECKED

SIZE

REV. NO.

DWG NO.

PART NO.

C

SCALE

RELEASE DATE

SHEET     OF

ENGINEERING

DRAWN

DATE

THIRD ANGLE PROJECTION

Vessel Vent Connection

Can be connected to the outlet vent, 

facility vent, or independently vented to 

atmosphere

Summary of Contents for Trapzilla TZ-1826

Page 1: ...HOLE OR PART WITHOUT WRITTEN CONSENT FROM THERMACO INC POSSESSION OF THIS DRAWING DOES NOT CONSTITUTE THE RIGHT TO MANUFACTURE POSSESSION OF THIS DRAWING DOES CONSTITUTE AN IMPLIED NONDISCLOSURE AGREE...

Page 2: ...There are many factors influencing odor evolution and dissemination These include room ventilation kitchen menu ambient temperatures ware washing practices grease oil input daily input fluid volume sa...

Page 3: ...andard STC 22 cover Each TZ 1826 would require two 2 FTCA 22 covers SSA 1826 Support Stand for TZ 1826 forAbove Ground Installations Must be fully supported not to be installed over grates Included wi...

Page 4: ...diameter of the system s outlet connection must be present as close as possible to the Trapzilla outlet to prevent possible siphonage problems The Vent on the Outlet piping is to be installed in accor...

Page 5: ...ut before and after all Trapzilla Installations Outlet Inlet Cleanout Cleanout Outlet Vent Connect to facility vent Note Drawing for reference only Equipment must be installed in compliance with all a...

Page 6: ...ts Connect to facility vent Low Head Flow Control not pictured to be installed as close as possible to inlet of first grease interceptor Cleanout Note Drawing for reference only Equipment must be inst...

Page 7: ...ESS NOTED 646 GREENSBORO STREET PO BOX 2548 ASHEBORO NC 27203 VOICE 336 629 4651 FAX 336 626 5739 Decimals XX 03 XXX 015 Unless otherwise specified Dimensions are in inches Tolerances Angular 1 CHECKE...

Page 8: ...it may also be installed in the ground inside or outside of the facility For instances where the facility drainage piping requires an extension collar that is more than the 18 provided by the built in...

Page 9: ...s purchased separately In some cases TZ 1826 may be installed in locations where built in extension collar will not reach grade In these cases the two piece ECA TZ 29 Extension Collar purchased separa...

Page 10: ...dapter ring Two of these screws should be installed in each of the four 4 skirt areas of the adapter ring Check the extension collar height dimension frequently during this operation to ensure that th...

Page 11: ...bolts and fully remove the 22 lid to pump out It is not necessary to remove adapter lid to pump out Trapzilla 2 Begin by taking the grease from the top of the main chamber until all grease is removed...

Page 12: ...not arising out of defects in workmanship or materials Thermaco shall not be responsible for damage to Products resulting from ultraviolet light exposure vault flooding sewer line back up pumping or...

Reviews: