©2001 Thermaco, Inc. All rights reserved • Patented/Patents Pending • Specifications subject to change without notice
Thermaco, Inc. • 646 Greensboro St. • Asheboro, N. C. 27204-2548 • Phone (336) 629-4651
MNL-AST 8
®
AST
Clearing Macerator Pump Jams
If Macerator Pump Jams,
1 - Disconnect power to AST Unit
2 - Remove macerator pump cover
3 - Remove jam wrench (A) attached to top of macerator pump
4 - Remove black plug covering socket (B) at the center of the pump
5 - Insert jam wrench into socket at center of the pump (B)
6 - Turn jam wrench in either direction to clear jam
7 - Remove jam wrench from the socket
8 - Replace jam wrench
9 - Replace black plug into socket (B)
10 - Replace macerator pump cover
B
To Electrical Source
Macerator Pump Top
A