4
Ultra-Aire XT105H Installation Instructions
www.Ultra-Aire.com | 1-800-533-7533
SPECIFICATIONS
Part Number:
4032240
Blower:
257 CFM @ 0.0" WG
206 CFM @ 0.2" WG
146 CFM @ 0.4" WG
Power:
530 Watts @ 80°F and 60% RH
Supply Voltage:
115 VAC – 1phase – 60 Hz
Current Draw:
4.9 Amps
Circuit Requirement:
15 Amp Dedicated
Energy Factor:
4.2 L/kWh
Operating Range:
56°F Min, 95°F Max (Inlet Air Temperature)
Sized for:
Up to 2,500 Sq. Ft. - Typical
Minimum Performance at: 80°F and 60% RH
70°F and 60% RH
Water Removal:
105 pints/day
85 pints/day
Efficiency:
8.8 Pints/kWh
8.0 Pints/kWh
Duct Connections:
6" Round Inlet; 10" Round Inlet; 10" Oval Outlet
Air Filter:
MERV-11, Standard Pleat
Efficiency:
65% ASHRAE Dust Spot
Size:
16" x 20" x 2"
Optional Air Filter:
MERV-14, Embossed Pleat (will need filter housing)
Efficiency:
95% ASHRAE Dust Spot
Size:
20" x 24" x 4"
Power Cord:
9', 115VAC, Ground
Internal Insulated Cabinet:
Yes
Drain Connection:
3/4" Threaded Female NPT
Refrigerant Type:
R410A (Refer to manufacturers label for more information)
Refrigerant Amount:
1 lb., 10 oz.
Dimensions:
Unit With Collars
Unit Without Collars
Shipping
Width:
20 1/4"
20 1/4"
25"
Height:
21 3/4"
21 3/4"
28"
Length:
41 1/2"
37 3/4"
42"
Weight:
140 lbs.
139 lbs.
162 lbs.
FRONT
20 1/4
"
21 3/4
"
21 3/4
"
41 1/2
"
37 3/4
"
21 3/4
"
21 3/4
"
BACK
20 1/4
"
6
"
Diameter
10
"
Diameter
10
"
Diameter
SIDE VIEW
BACK VIEW
FRONT VIEW
403593
6