Therma-Stor Ultra-Aire DEH 3000 Installer'S & Owner'S Manual Download Page 6

4.3 Humidity Control Adjustment

Set the humidity control to the desired humidity level for the home. 
The dehumidifier will run continuously until the relative humidity 

(RH) is reduced to the humidity control 
dial setting. Setting the humidity control to 
lower RH levels will NOT increase the unit's 
dehumidification rate; the unit will simply run 
longer to reduce the area's RH to the setting. 
The Ultra-Aire unit (and refrigerant based 
dehumidifiers in general) will reduce a warm 
space's RH to a lower level than that of a 
cool space. It is therefore pointless to set the 

humidity control to excessively low levels in cool rooms; doing so 
will result in long periods of ineffective dehumidifier run time.

Quality humidity meters are available from the factory and are 
recommended to accurately monitor humidity levels.

4.4 Fan/Filter Switch

Turning ON the fan/filter switch will cause the central conditioning 
unit's internal fan to run continuously, whether the central 

conditioning unit is dehumidifying or not. 
This function is desirable if the central 
conditioning unit is used for air circulation 
and filtration. When the switch is ON, air will 
be constantly filtered through the central 
conditioning unit and circulated throughout 
the house. When the switch is OFF, the fan 
will operate only when the humidity control 

calls for dehumidification or when the ventilation timer calls for 
ventilation.

4.5 Ventilation Timer

The ventilation timer controls the fan and the motorized fresh 
air damper. When the ventilation timer is activated, the central 
conditioning unit will circulate the indoor air, and bring in fresh air 
from outside. The ventilation timer should be set for the required 
ventilation of the residence. The home should be ventilated with 
fresh air whenever it is occupied. 

The ventilation timer is an electronic timer that displays the current 
time. This timer has a battery backup, so it will not require resetting 
after a power outage. The one minute time increments of the 
ventilation timer allow you to program the ventilation of your home 
to fit your schedule.

The ventilation timer has six programs with each program having 
one “on” and one “off” event. A program allows the user to turn the 
ventilation on at a certain day and time, then it allows them to turn 
the ventilation off at a certain day and time. Each of these programs 
can be repeated daily or weekly or during a specified block of days. 
All six of the programs operate independently of each other.

If the timer fails to operate or operates erratically, check that 
the control panel receives 24Vac from the Ultra-Aire . If 24Vac is 
present at the control panel, reset the timer by pressing the reset 
button at the bottom center of the timer face. The reset button is 
the small recessed button with an R beneath it located below the 
1…7 and h buttons. Press the reset button in until the display 
disappears. Release the reset button. The display will reappear 
as 00:00. Resetting the timer will clear the time and all program 
settings. After resetting the timer, follow the instructions below to 
set the correct time and ventilation programs.

The following instructions explain how to set the ventilation timer. 
First, set the correct time on the timer by sliding the switch in 
the upper right hand corner of the timer to the clock  
and pressing the 1…7 (DAY), h (HOUR), and m (MINUTE) buttons. 
Remember that this timer operates on a 24-hour (military time) 
clock.

Next, set the ventilation time schedule. Slide the switch in the 
upper right hand corner to the program symbol P “ON” will appear 
to the right of the time and the number “1” will appear in the lower 
right hand corner of the display. The “1” and “ON” signify the turn 
on time for the first program. Press the 1…7 button to choose 
the days of the week for this program. You can choose Mon-Sun 
Mon-Fri, Sat-Sun, or any single day of the week. The days chosen 
are shown along the top of the display on the ventilation timer. Next 
press the h button to set the hour for the start of the ventilation 
period. Remember that this timer operates on a 24-hour clock. 
Then press the m button to set the minutes past the hour to start 
the ventilation. Now, with the ventilation start time set, press the 
I/O button. The word “OFF” should appear to the right of the time 
and the number “1” should remain in the lower right hand corner of 
the display. The “1” and “OFF” signify the turn off time for the first 
program. Set the turn off time using the 1…7, h, and m buttons in 
the same way as described above and continue on to the second 
through sixth programs. When setting the ventilation programs, 
you can return to the current time display by sliding the switch in 
the upper right corner of the timer to RUN. The slide switch in the 
upper right must be set to RUN for the timer to operate with the 
scheduled programs.

The slide switch in the upper left of the timer is used to choose 
between automatic and manual operation of the timer relay. When 
the slide switch in the upper left of the timer is set to AUTO mode, 
the central conditioning unit will ventilate when the scheduled 
programs call for ventilation. When the slide switch in the upper 
left of the timer is set to manual (set to hand symbol on the the 
right), the operation of the timer is controlled by the I/O button only. 
Pressing the I/O button will switch the ventilation timer between 
ON (detent) and OFF (detent). As you press the I/O button, “ON” or 
“OFF” will be displayed to the right of the time. The “ON” or “OFF” 

Figure 4

Fan/Filter Switch

6

7

Ultra-Aire 100V Installer’s & Owner’s Manual

Ultra-Aire 100V Installer’s & Owner’s Manual

FOR HVAC INSTALLER ONLY

Figure 3

Humidity Control 

Adjustment Knob

Summary of Contents for Ultra-Aire DEH 3000

Page 1: ...fresh outdoor air may be ducted to the unit via a six inch round duct This provides fresh air to dilute pollutants and maintain high oxygen content in the air The amount of fresh air ventilation can...

Page 2: ...your Ultra Aire indoor air quality system Read and save these instructions The device is designed to be installed INDOORS IN A SPACE THAT IS PROTECTED FROM RAIN AND FLOODING Install the unit with spa...

Page 3: ...building supply plumbing and hardware stores It will slide tightly inside the end of the drain hose If more than one length of pipe is required they can be joined with a short piece cut from the end o...

Page 4: ...calling 1 800 533 7533 for recommendations regarding the use of higher flows with your specific application The outside air duct should be connected to the 6 round collar on top of the unit The 6 roun...

Page 5: ...ake sure none of the compressor tubes are pressed against the cabinet or front panel A length of 10 feet or more of acoustical flex ducting on the outlet of the Ultra Aire will reduce air noise from t...

Page 6: ...r of the timer face The reset button is the small recessed button with an R beneath it located below the 1 7 and h buttons Press the reset button in until the display disappears Release the reset butt...

Page 7: ...pot Test Method 52 76 This filter is much more efficient than the standard air filter and is able to catch much smaller particles that can aggravate allergies The high efficiency air filter is 4 inche...

Page 8: ...the unit to contact the red lead or the white lead from the unit or damage to the transformers will result Do not direct connect the white lead on the unit to the violet lead on the ventilation contro...

Page 9: ...Range Accuracy 10 95 RH 5 Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 Size 4 95 L x 1 06 W x 4 19 H Major Operations n Digital control of Relative Humidity Digital Set Point n...

Page 10: ...n handling the high efficiency pleated paper filter Do not attempt to clean the high efficiency pleated paper filter It should be replaced when it becomes restrictive See Figure 7 7 Service CAUTION Se...

Page 11: ...or the correct charge weight and refrigerant type 7 5 Fan Replacement The centrifugal fan has a PSC motor and internal thermal overload protection If defective the complete assembly must be replaced 1...

Page 12: ...t carbon deposits the burn out occurred while the compressor was not rotating Contaminants are therefore largely confined to the compressor housing A single installation of liquid and suction line fil...

Page 13: ...gerant suction tube between the accumulator and the compressor It will automatically shut the compressor off if the low side refrigerant temperature drops due to excessive frost formation on the evapo...

Page 14: ...ULTRA AIR 100V ELECTRICAL SCHEMATIC 14 Ultra Aire 100V Installer s Owner s Manual...

Page 15: ...ULTRA AIRE 100V PICTORIAL ELECTRICAL DIAGRAM 15 Ultra Aire 100V Installer s Owner s Manual...

Page 16: ...anasonic 2R12S3R126A 6A 10 4022144 1 Compressor Overload TI MRA98706 673 not shown 11 4021396 1 Condenser Coil 12 4022445 1 Cord Wire Harness 13 4025087 1 Filter Drier 14 4021626 1 Hose Drain Pan 56 I...

Page 17: ...32 4024153 1 Cover for Items 28 29 not shown 33 4021495 1 Knob Black 25 shaft 34 4024150 1 Instructions Humidity Fan not shown 35 4024122 1 Instructions Ventilation Timer Humidity not shown 36 4025560...

Page 18: ...ULTRA AIRE 100V EXTERNAL INSULATION KIT 18 Ultra Aire 100V Installer s Owner s Manual...

Page 19: ...rough the rubber grommet 4 Place the box in the hole and put the mounting tabs through the slots in the box sides as shown 5 Place the two 3 4 long 8 screws through the tab slots and into the holes in...

Page 20: ...costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsib...

Page 21: ...rmastor com Information in this document is subject to change without notice No part of this document may be reproduced or transmitted in any form or by any means electronic or mechanical for any purp...

Reviews: