Therma-Stor Ultra-Aire DEH 3000 Installer'S & Owner'S Manual Download Page 11

No dehumidification, compressor does not run but fan runs 
with fan switch and ventilation timer OFF and humidity control 
turned to ON.

1.  Defective compressor run capacitor (Sec. 5.6).
2.  Loose connection in compressor circuit (See Fig. 4).
3.  Defective compressor overload (Sec. 5.6A).
4.  Defective compressor (Sec. 5.6).
5.  Defrost thermostat open (Sec. 5.8).

Fan runs with fan switch and ventilation timer OFF, but 
compressor cycles on & off.

1.   Low ambient temperature and/or humidity causing unit to 

cycle through defrost mode.

2.  Defective compressor overload (Sec. 5.6A).
3.  Defective compressor (Sec. 5.6).
4.  Defrost thermostat defective (Sec. 5.8).
5.  Dirty air filter(s) or air flow restricted.

Fan does not run with fan switch in either position. Fan does 
not run with ventilation timer activated. Compressor runs 
briefly but cycles on & off with humidity control turned to ON.

1.  Loose connection in fan circuit (See Fig. 4).
2.  Obstruction prevents fan impeller rotation.
3.  Defective fan.
4.  Defective fan relay.

Fan runs with fan switch ON. Fan does not run with ventilation 
timer activated.

1.  Defective ventilation timer.
2.  Time not correct on ventilation timer.
3.  Ventilation timer set to manual & switched OFF.

Evaporator coil frosted continuously, low dehumidifying 
capacity.

1.  Defrost thermostat loose or defective (Sec. 5.8).
2.  Low refrigerant charge
3.  Dirty air filter(s) or air flow restricted.
4.  Excessively restrictive ducting connected to unit.

Unit not providing ventilation. Ventilation timer notoperating 
correctly.

1.   If timer is not functioning correctly, reset timer and 

reprogram (Sec. 3.5)

2.   Check control wire connections (check connections at 

damper also)

3.  Defective fresh air damper (Sec. 5.9)

7.4 Refrigerant Charging

If the refrigerant charge is lost due to service or a leak, a new 
charge must be accurately weighed in. If any of the old charge is 

left in the system, it must be recovered before weighing in the new 
charge. Refer to the unit nameplate for the correct charge weight 
and refrigerant type.

7.5 Fan Replacement

The centrifugal fan has a PSC motor and internal thermal overload 
protection. If defective, the complete assembly must be replaced.

1.  Unplug the power cord.
2.  If an outlet duct is connected to the unit, remove it.
3.  Remove the cabinet side.
4.   Remove the 3 screws attaching the electrical box located in 

front of the fan to the base.

5.   Disconnect the fan leads. Black from the fan relay and white 

from the run capacitor.

6.   Remove the nuts & bolts holding the fan outlet flange to the 

cabinet end and remove the fan.

7.  Reassemble the new fan by reversing the above procedure.

7.6 Compressor/Capacitor Replacement

This compressor is equipped with a two terminal external overload 
and a run capacitor, but no start capacitor or relay (See Figure 4).

CAUTION-ELECTRICAL SHOCK HAZARD: 

Electrical power must be present to perform 

some tests. These tests should be performed 

by a qualified service person.

7.6A Checking Compressor Motor Circuits

Perform the following tests if the fan runs but the compressor does 
not with the fan switch OFF and the humidity control ON.

1.   Unplug the unit, remove the cabinet side and the electrical 

connection cover on the compressor top.

2.    Plug in the unit and turn the humidity control to ON. Check 

for 110 volts from compressor terminal R to overload 
terminal 3 using an AC voltmeter. If voltage is present, go to 
step 3. If no voltage, there may be a loose connection in the 
compressor circuit. Test each component for continuity. See 
the appropriate section if a defect is suspected.

3.    Unplug the unit, then disconnect the red and yellow wires 

from compressor terminals R & S. Using an ohmmeter, 
check continuity between the points listed below.

4.    Compressor terminals C and S:  

No continuity indicates an open start winding. The 
compressor must be replaced. Normal start winding 
resistance is 3 to 7 ohms.

5.    Compressor terminals C and R: 

No continuity indicates an open run winding. The 
compressor must be replaced. Normal run winding 
resistance is .5 to 2 ohms.

FOR HVAC INSTALLER AND HOMEOWNER

11

Ultra-Aire 100V Installer’s & Owner’s Manual

Summary of Contents for Ultra-Aire DEH 3000

Page 1: ...fresh outdoor air may be ducted to the unit via a six inch round duct This provides fresh air to dilute pollutants and maintain high oxygen content in the air The amount of fresh air ventilation can...

Page 2: ...your Ultra Aire indoor air quality system Read and save these instructions The device is designed to be installed INDOORS IN A SPACE THAT IS PROTECTED FROM RAIN AND FLOODING Install the unit with spa...

Page 3: ...building supply plumbing and hardware stores It will slide tightly inside the end of the drain hose If more than one length of pipe is required they can be joined with a short piece cut from the end o...

Page 4: ...calling 1 800 533 7533 for recommendations regarding the use of higher flows with your specific application The outside air duct should be connected to the 6 round collar on top of the unit The 6 roun...

Page 5: ...ake sure none of the compressor tubes are pressed against the cabinet or front panel A length of 10 feet or more of acoustical flex ducting on the outlet of the Ultra Aire will reduce air noise from t...

Page 6: ...r of the timer face The reset button is the small recessed button with an R beneath it located below the 1 7 and h buttons Press the reset button in until the display disappears Release the reset butt...

Page 7: ...pot Test Method 52 76 This filter is much more efficient than the standard air filter and is able to catch much smaller particles that can aggravate allergies The high efficiency air filter is 4 inche...

Page 8: ...the unit to contact the red lead or the white lead from the unit or damage to the transformers will result Do not direct connect the white lead on the unit to the violet lead on the ventilation contro...

Page 9: ...Range Accuracy 10 95 RH 5 Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 Size 4 95 L x 1 06 W x 4 19 H Major Operations n Digital control of Relative Humidity Digital Set Point n...

Page 10: ...n handling the high efficiency pleated paper filter Do not attempt to clean the high efficiency pleated paper filter It should be replaced when it becomes restrictive See Figure 7 7 Service CAUTION Se...

Page 11: ...or the correct charge weight and refrigerant type 7 5 Fan Replacement The centrifugal fan has a PSC motor and internal thermal overload protection If defective the complete assembly must be replaced 1...

Page 12: ...t carbon deposits the burn out occurred while the compressor was not rotating Contaminants are therefore largely confined to the compressor housing A single installation of liquid and suction line fil...

Page 13: ...gerant suction tube between the accumulator and the compressor It will automatically shut the compressor off if the low side refrigerant temperature drops due to excessive frost formation on the evapo...

Page 14: ...ULTRA AIR 100V ELECTRICAL SCHEMATIC 14 Ultra Aire 100V Installer s Owner s Manual...

Page 15: ...ULTRA AIRE 100V PICTORIAL ELECTRICAL DIAGRAM 15 Ultra Aire 100V Installer s Owner s Manual...

Page 16: ...anasonic 2R12S3R126A 6A 10 4022144 1 Compressor Overload TI MRA98706 673 not shown 11 4021396 1 Condenser Coil 12 4022445 1 Cord Wire Harness 13 4025087 1 Filter Drier 14 4021626 1 Hose Drain Pan 56 I...

Page 17: ...32 4024153 1 Cover for Items 28 29 not shown 33 4021495 1 Knob Black 25 shaft 34 4024150 1 Instructions Humidity Fan not shown 35 4024122 1 Instructions Ventilation Timer Humidity not shown 36 4025560...

Page 18: ...ULTRA AIRE 100V EXTERNAL INSULATION KIT 18 Ultra Aire 100V Installer s Owner s Manual...

Page 19: ...rough the rubber grommet 4 Place the box in the hole and put the mounting tabs through the slots in the box sides as shown 5 Place the two 3 4 long 8 screws through the tab slots and into the holes in...

Page 20: ...costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsib...

Page 21: ...rmastor com Information in this document is subject to change without notice No part of this document may be reproduced or transmitted in any form or by any means electronic or mechanical for any purp...

Reviews: