bedroom.

2.4 Hanging the Ultra-Aire Quiet Vent

The Ultra-Aire Quiet Vent has four vibration absorbing straps 
for hanging from joists, rafters, or trusses and use (4) 1/4" 
diameter lag bolts or the equivalent. Locate the unit to 
minimize the ducting from the baths and kitchen to the Ultra-
Aire Quiet Vent inlets and from the Ultra-Aire Quiet Vent outlet 
to the outside. 

2.5 Ducting to and from the Ultra-Aire Quiet 

Vent

All flexible ducting connected to the unit should be UL listed. 
The preferred method of ducting the exhaust air from the 
rooms is to use 4" round duct from 4" x 6" register heads 
located in the wall cavities or the ceiling. For routing through 
3.5" stud cavities, flatten the 4" round duct to 3.25". If a 
4" duct length from a full bath or kitchen exceeds 50’, two 
4" ducts or a 6" duct is recommended. The 4" duct can be 
either metal or flexible and can be routed to the Ultra-Aire 
Quiet Vent 4" inlet or manifolded to a 6" duct. If more than 
four 4" ducts are connected to the Ultra-Aire Quiet Vent, use 
a 6" manifold on the Ultra-Aire Quiet Vent’s 6" inlet.

DO NOT locate the register head connecting the kitchen 

duct to the Ultra-Aire Quiet Vent in the area designated in 

Fig. 2.

To exhaust the stale air, connect a six inch insulated 
flexible duct from the outlet of the Ultra-Aire Quiet Vent to a 
dampered six inch wall cap. If the length of the exhaust duct 

exceeds 50 ft., an 8" duct should be used. All the ducts must 
be insulated when they are located in non-heated space in 
a cold climate. Flexible duct can be spliced by threading the 
ends of the ducts into each other 3 turns. To reduce leakage, 
all the duct couplings should be taped with 3 turns of duct 

tape. Several ducting alternatives are illustrated in Fig. 1.

2.6 Wiring the Ultra-Aire Quiet Vent

NOTE: All electrical connections must be installed by a qualified 
electrician. All wiring must conform to the local electric codes 
and/or the National Electrical Code.

Ultra-Aire Quiet Vent uses a 115 volt, 10 amp circuit which 
is connected to the black and white wires in the electrical 
cabinet (see Fig. 3). Spring wound one hour remote timers 
or humidity controllers located in the baths and kitchen are 
wired in parallel to the two blue wires. These remote controls 

FOR HVAC INSTALLER ONLY

4

Ultra-Aire Quiet Vent Installer’s & Owner’s Manual

Timer Switch

Ground

Timer Switch

Ground

Circuit to Next Timer
In Bath or Kitchen

115 Volt Circuit/Ground
From Quiet Vent to Bath or Kitchen

10-15 Amp 115 Volt 
Circuit With Ground 
From Main Electrical
Service

Cooking Area

Do Not Install Above or Inside 

This Area

Cooking

Equipment

 

45°

45°

Floor

Summary of Contents for Quiet-Vent Ventilation System

Page 1: ...680 Madison WI 53708 TOLL FREE 1 800 533 7533 www thermastor com sales thermastor com TS 174B INSTALLER S OWNER S MANUAL HVAC INSTALLER PLEASE LEAVE MANUAL FOR HOMEOWNER P N 4019663 Serial No ________________________ Install Date ___________ Sold by ...

Page 2: ... reduce the risk of fire electric shock or injury to persons observe the following A Installation work and electrical wiring must be done by qualified person s in accordance with all applicable codes and standards including fire rated construction B Sufficient air is needed for proper combustion and exhausting of gases through the flue chimney of fuel burning equipment to prevent backdrafting Foll...

Page 3: ... from the Ultra Aire Quiet Vent see paragraph F In cold climates the unit should be located in a heated space to prevent condensation from forming inside the cabinet A basement or utility room is an ideal location If the Ultra Aire Quiet Vent and its ducting must be located in a unheated space in a cold climate they must be insulated to prevent condensation from forming in the system If the Ultra ...

Page 4: ... stale air connect a six inch insulated flexible duct from the outlet of the Ultra Aire Quiet Vent to a dampered six inch wall cap If the length of the exhaust duct exceeds 50 ft an 8 duct should be used All the ducts must be insulated when they are located in non heated space in a cold climate Flexible duct can be spliced by threading the ends of the ducts into each other 3 turns To reduce leakag...

Page 5: ...ired to control moisture and odors additional spades can be moved in If the home becomes too dry decrease the hours of low speed operation 3 2 Using Remote Timers Estimate the ventilation time required and set it on the timer Activate the timer whenever moisture or odors are generated in the room If timers are not available locally they may be ordered with the Ultra Aire Quiet Vent 3 2 Adjusting t...

Page 6: ...the segments on the 7 day timer are moved to the center of the dial thus calling for low speed ventilation If the blower does not run with the segments in and the optional controls off check for voltage between timer terminal 5 and ground If terminal 5 does not have voltage the timer is defective If terminal 5 has voltage and relay terminal 5 does not have voltage the relay is defective If relay t...

Page 7: ...y the period of time if any that the Ultra Aire Quiet Vent is out of service while awaiting covered warranty service UPON THE EXPIRATION OF THE WRITTEN WARRANTY APPLICABLE TO THE Ultra Aire Quiet Vent VENTILATING SYSTEM OR ANY PART THEREOF ALL OTHER WARRANTIES IMPLIED BY LAW INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE SHALL ALSO EXPIRE ALL WARRANTIES MADE BY THERMA STOR LLC ARE ...

Page 8: ...any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2008 Therma Stor LLC All rights reserved PO Box 8680 Madison WI 53708 Phone 608 222 5301 Fax 608 222 1447 Web www thermastor com Email sales thermastor com Ultra Aire Quiet Vent Installer s Owner s Manual ...

Reviews: