3.3.20 Diagnostic Mode - Refrig. Test
The display will communicate to the user the following
information during a Refrigeration Test:
Inlet = Temperature and RH/Grains
Outlet = Temperature and RH/ Grains
Hours = Life hours only.
Evaporator Coil = Temperature
Countdown timer = 20 minutes
Once the 20 minute countdown timer has expired, the
display will automatically advance to show the refrigeration
test results. The display will communicate to the user either
“Refrig. test passed” or “Refrig. test failed”.
Press the Next button to return to the first diagnostic test or
press and hold the Next button for 3 seconds to return to the
Dashboard.
3.4 Condensate Removal
The Phoenix Dry Max is equipped with an internal
condensate pump to remove the water that is condensed
during dehumidification. This allows the condensate to
be pumped up to 20 feet with the attached hose. If the
condensate must be pumped more than 20 feet above the
unit, a second pump must be added to relay the condensate.
The condensate pump automatically purges when the
reservoir is full. Use the PURGE button to manually remove
condensation.
3.5 Ducting
A wire duct collar is supplied to allow 10” lay-flat duct to
be attached to the Phoenix Dry Max outlet. Lay-flat plastic
ducting is available; see section 6 Options and Accessories.
To attach ducting to the wire duct collar, put the plastic duct
end through the collar center and roll the duct end outward
so that it overlaps the outside of the collar. The duct and
collar may then be quickly attached to the Phoenix Dry Max
by snapping the collar over the four exhaust tabs.
3.6 Defrost Cycle
If the low side refrigerant temperature drops due to excessive
frost formation on the evaporator coil and below the
temperature set point, the thermistor activates the PLC and
Status Light Indicator. The compressor is cycled off and on by
the thermistor temperature measurement. The air mover will
continue to run, causing air to flow through the evaporator
coil and melt the ice when the compressor is off. When the
air temperature and/or humidity increases, the evaporator
temperature will rise and the thermistor will end the defrost
cycle at the temperature set point
3.7 POWER Button
When the dehumidifier is plugged in it will enter stand-by
mode.
Press the
button to turn the dehumidifier on. The unit
will begin the Powering Up sequence and you will see this
screen:
Press and hold the
to turn the dehumidifier off. The
dehumidifier will go through a powering-down cycle.