THERMAL SHUT OFF
This is a safety feature for Thermostatic valves
manufactured to Australian Standard AS4032.4
-
2014
Basic terms, should the Cold or Hot water supply suddenly fail,
the mixing valve will shut off , preventing harm or
thermal shock.
This valve CT100 complies with Clauses 4.4.2 and 4.4.3 of the above standard.
Explanation as written in the standard AS4032.4 as follows;
Cold water isolation
When tested in accordance with Appendix D, the thermal shut
-
off under cold
water isolation of each thermostatic tap, when pre
-
adjusted to supply mixed
water at temperatures of 38
+/
-
2°C, 45
+/
-
2°C and the manufacturer
’
s nominated
maximum setting, shall not exceed the temperature rises and durations given in
Table 4.1 during both the period of shut
-
off of the cold water supply and
immediately following the restoration of the cold water supply.
The mixed water shall stabilize to within 2°C of the preset temperature, in not
more than 20.0 seconds following restoration of the cold water supply.
Heated water isolation
When tested in accordance with Appendix D, the thermal shut
-
off under heated
water isolation of each thermostatic tap, when pre
-
adjusted to supply mixed
water at
temperatures of 38
+/
-
2°C, 45
+/
-
2C and the manufacturer
’
s nominated
maximum setting, shall not exceed the temperature rises and durations given in
Table 4.1. of the standard AS4032.4
The amount of water discharged following thermal shut
-
off under heated water
isolation of each thermostatic tap shall not exceed 0.75 L within
5
–
35
seconds
following heated water supply isolation.
The mixed water shall stabilize to within 2°C of the preset temperature, in not
more than 20.0 seconds following restoration of the heated water supply
.
Page 10
Operating
Temp °C
Dynamic
Pressures kPa
Nominated Cold water
Supply 15+5°C
Nominated Hot water
Supply 65+2°C
Nominated Cold water
Supply 300+10 kPa
Nominated Hot water
Supply 300+10 kPa
Temp Set
Actual
Actual
Actual
Actual
38+1°C
16.2
63.7
303
301
45+1°C
18.5
63.2
302
298
Operating
Temp °C
Dynamic
Pressures kPa
Nominated Cold water
Supply 15+5°C
Nominated Hot water
Supply 65+2°C
Nominated Cold water
Supply 300+10 kPa
Nominated Hot water
Supply 300+10 kPa
Temp Set
Actual
Actual
Actual
Actual
38+1°C
17.3
64.9
302
298
45+1°C
17.2
65.0
300
301
Dynamic pressure ration , after Hot water isolation endurance test
Dynamic pressure ration , after Cold water isolation endurance test