6
The following control commands can be triggered
with the remote control:
Control
command
Description
Can be
triggered by
SendoPro
868-A/
theSenda B
(app)
Can be
trigge-
red by
the-
Senda P
Teach-in chan-
nel A
Activation
x
x
Switching light
Lighting group can be switched
on and off.
x
x
Presence test
On/Off
x
x
Restart
Restart detector
x
x
Factory settings Set all parameters and settings
to factory setting.
x
Detection zone
The detection area is divided into two independent detection
zones (see 5. Detection area). For a maximum range, zone 1
and zone 2 are activated. If a limitation of the detection area
is required, zone 1 or zone 2 can be deactivated.
Value range
Adjustable values "SendoPro 868-A"/"theSenda B"
(app)
Z1, Z2, Z1 and Z2
Brightness setpoint channel A light
Brightness setpoint A defines the minimum desired bright
-
ness. The currently prevailing brightness is measured under
-
neath the presence detector. If the prevailing brightness is
below the setpoint value, the light is switched on when a
presence is detected (in configuration type fully automatic
device).
Value range
Adjustable values "SendoPro 868-A"/"theSenda B" (app)
30–3000 lux
Adjustable values "theSenda P"
30, 300, 500,
800 lux
Deactivation of brightness measurement (brightness
measurement has no effect)
The light channels only switch according to presence and
absence.
"SendoPro 868-A"/"theSenda B" (app)
Measurement
off
"theSenda P"
Button
Teach-in channel A light
During teach-in, the currently measured brightness value is
accepted as brightness setpoint value A. Values outside the
permitted range will automatically be set to the appropriate
limit value.
"SendoPro 868-A"/"theSenda B" (app)
Teach-in
"theSenda P"
Button
Room correction factor lighting A
The room correction factor is a measurement for the diffe-
rence of the brightness measurement on the ceiling and the
work area. The brightness measurement value at the ceiling
is influenced by the installation location, incidence of light,
position of the sun, weather conditions, the reflection proper
-
ties of the room, and the furniture.
With the room correction factor, the brightness measurement
value of lighting channel A is adjusted to the conditions in the
room and in this way can be matched to the lux meter value
measured at the surface beneath the presence detector.
Room correction factor = Brightness value at the ceiling/
brightness value at the working surface
Using management "SendoPro 868-A" remote control and lux
meter:
•
The lux meter is placed on the work surface below the
sensor and the measured lux value is entered via the
"SendoPro 868-A" remote control, <brightness measure-
ment value A>.
•
The room correction factor is calculated from this auto-
matically. Values between 0.05 and 2.0 are permitted.
Calculated or entered values outside the permitted range
will automatically be set to the appropriate limit value.
•
The calculated room correction factor will be applied
immediately. For monitoring purposes, the room correc
-
tion factor can be queried via the <room correction factor
A> parameter.
Using "theSenda B" remote control and "theSenda Plug" app:
•
Connect "theSenda B" remote control with the corres-
ponding "theSenda Plug" app.
•
Select the appropriate detector type and load the parame-
ter set.
•
Press the send button at the <brightness measurement
value A> parameter.
•
Follow the instructions of the app.
•
The room correction factor is calculated from this auto-
matically. Values between 0.05 and 2.0 are permitted.
Calculated or entered values outside the permitted range
will automatically be set to the appropriate limit value.
•
The calculated room correction factor will be applied
immediately. For monitoring purposes, the room correc
-
tion factor can be queried via the <room correction factor
A> parameter.
The standard value is 0.3 and is suitable for most applications.
Changes are only sensible in strongly deviating situations.
Detection sensitivity
The detector has 5 sensitivity increments. The basic setting
is the middle increment (3). By selecting the test presence
operating mode, the set sensitivity increment is not changed.
With the "SendoPro 868-A" management remote control, as
well as with "theSenda B" app remote control (with "the-
Senda Plug" app), the increments 1 to 5 can be selected
and sent to the detector. With the "theSenda P" installation