background image

6

The following control commands can be triggered 

with the remote control:

Control 

command

Description

Can be 

triggered by 

SendoPro 

868-A/ 

theSenda B 

(app)

Can be 

trigge-

red by 

the-

Senda P

Teach-in chan-

nel A

Activation

x

x

Switching light

Lighting group can be switched 

on and off.

x

x

Presence test 

On/Off

x

x

Restart

Restart detector

x

x

Factory settings Set all parameters and settings 

to factory setting.

x

Detection zone

The detection area is divided into two independent detection 

zones (see 5. Detection area). For a maximum range, zone 1 

and zone 2 are activated. If a limitation of the detection area 

is required, zone 1 or zone 2 can be deactivated.

Value range

Adjustable values "SendoPro 868-A"/"theSenda B" 

(app)

Z1, Z2, Z1 and Z2

Brightness setpoint channel A light

Brightness setpoint A defines the minimum desired bright

-

ness. The currently prevailing brightness is measured under

-

neath the presence detector. If the prevailing brightness is 

below the setpoint value, the light is switched on when a 

presence is detected (in configuration type fully automatic 

device).

Value range

Adjustable values "SendoPro 868-A"/"theSenda B" (app)

30–3000 lux

Adjustable values "theSenda P"

30, 300, 500, 

800 lux

Deactivation of brightness measurement (brightness 

measurement has no effect)

The light channels only switch according to presence and 

absence.

"SendoPro 868-A"/"theSenda B" (app)

Measurement 

off

"theSenda P"

Button 

Teach-in channel A light

During teach-in, the currently measured brightness value is 

accepted as brightness setpoint value A. Values outside the 

permitted range will automatically be set to the appropriate 

limit value.

"SendoPro 868-A"/"theSenda B" (app)

Teach-in

"theSenda P"

Button 

Room correction factor lighting A

The room correction factor is a measurement for the diffe-

rence of the brightness measurement on the ceiling and the 

work area. The brightness measurement value at the ceiling 

is influenced by the installation location, incidence of light, 

position of the sun, weather conditions, the reflection proper

-

ties of the room, and the furniture.

With the room correction factor, the brightness measurement 

value of lighting channel A is adjusted to the conditions in the 

room and in this way can be matched to the lux meter value 

 measured at the surface beneath the presence detector.

Room correction factor = Brightness value at the ceiling/

brightness value at the working surface

Using management "SendoPro 868-A" remote control and lux 

meter:

 

The lux meter is placed on the work surface below the 
sensor and the measured lux value is entered via the 
"SendoPro 868-A" remote control, <brightness measure-

ment value A>.

 

The room correction factor is calculated from this auto-

matically. Values between 0.05 and 2.0 are permitted. 

Calculated or entered values outside the permitted range 

will automatically be set to the appropriate limit value.

 

The calculated room correction factor will be applied 

immediately. For monitoring purposes, the room correc

-

tion factor can be queried via the <room correction factor 

A> parameter.

Using "theSenda B" remote control and "theSenda Plug" app:

 

Connect "theSenda B" remote control with the corres-

ponding "theSenda Plug" app.

 

Select the appropriate detector type and load the parame-

ter set.

 

Press the send button   at the <brightness measurement 

value A> parameter.

 

Follow the instructions of the app.

 

The room correction factor is calculated from this auto-

matically. Values between 0.05 and 2.0 are permitted. 

Calculated or entered values outside the permitted range 

will automatically be set to the appropriate limit value.

 

The calculated room correction factor will be applied 

immediately. For monitoring purposes, the room correc

-

tion factor can be queried via the <room correction factor 

A> parameter.

The standard value is 0.3 and is suitable for most applications. 

Changes are only sensible in strongly deviating situations.

Detection sensitivity

The detector has 5 sensitivity increments. The basic setting 

is the middle increment (3). By selecting the test presence 

operating mode, the set sensitivity increment is not changed. 

With the "SendoPro 868-A" management remote control, as 

well as with "theSenda B" app remote control (with "the-

Senda Plug" app), the increments 1 to 5 can be selected 

and sent to the detector. With the "theSenda P" installation 

Summary of Contents for thePassa P360-101 UP WH

Page 1: ... control theSenda B option and corres ponding app theSenda Plug iOS Android 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed persons under the guidance and supervision of a qualified electrician in accordance with the techni...

Page 2: ...ple are present or it is dark Channel H presence Channel H presence is used for HVAC control The switching response of the floating contact is influenced only by pre sence and not by brightness If the contact is closed the time delay will be restarted at every movement Push buttons or switches do not influence the contact Switch on delay The switch on delay prevents instantaneous switching on The ...

Page 3: ...ighting directly below the detector If the brightness measurement is deactivated chan nel A light only switches depending on presence brightness setpoint value set to on via potentiometer or set to mea surement off via remote control 1 8 m Suitable lamps The presence detector is designed for the operation of fluore scent compact fluorescent halogen and incandescent lamps as well as LEDs The maximu...

Page 4: ... L Light measurement only with the Master Parameters are only set on the Master Switch up to 10 detectors in parallel Use the phase with the same phase for all detectors Master thePassa P360 101 UP Slave thePassa P360 Slave UP Master Master parallel switching for several lighting groups Several Masters can be used in a parallel switching Each Master controls its lighting group according to its own...

Page 5: ... only closes when someone is present after expiry of the switch on delay 0 contact closes immediately if people are present Parameters and control commands via remote control The following parameters can be checked or changed via the remote control for support during start up as well as servicing Parameter Description Can be que ried by SendoPro 868 A theSenda B app Can be chan ged by SendoPro 868...

Page 6: ... the furniture With the room correction factor the brightness measurement value of lighting channel A is adjusted to the conditions in the room and in this way can be matched to the lux meter value measured at the surface beneath the presence detector Room correction factor Brightness value at the ceiling brightness value at the working surface Using management SendoPro 868 A remote control and lu...

Page 7: ...stable values 0 s no switch on delay 30 s 1 10 min Configuration type Fully automatic device The lighting is switched on and off automatically Due to presence absence and brightness SendoPro 868 A theSenda B app auto theSenda P Button A Semi automatic Lights must always be switched on manually Switching off occurs automatically by the presence detector due to absence or brightness SendoPro 868 A t...

Page 8: ...ment occurs the light and presence switch contacts close y y When no one is present the light switch contact opens after 10 s y y Brightness measurement deactivated detector does not react to brightness y y The detector reacts as in configuration type fully auto matic device even if semi automatic is set y y Teach in cannot be activated in test mode y y Test mode ends automatically after 10 min Th...

Page 9: ...e Flickering for 2 s The command sent from the remote control via infrared was accepted by the presence detector Lighting up briefly The command sent from the remote control via infrared was rejected by the presence detector The command is not valid Check the selected detector type or parameters on the SendoPro or in the app Fast flashing Error flashing The presence detector has found an error Fli...

Page 10: ...Details www theben de en theSenda B Item no 9070985 Details www theben de en theSenda S Item no 9070911 Details www theben de en 12 Contact Theben HTS AG Im Langhag 7b 8307 Effretikon SWITZERLAND Phone 41 52 355 17 00 Fax 41 52 355 17 01 Hotline Phone 41 52 355 17 27 hotline theben hts ch www theben hts ch All countries except Switzerland Theben AG Hohenbergstraße 32 72401 Haigerloch GERMANY Tel 4...

Reviews: