background image

5

Setting of switch contact A light     

Potentiometer - Brightness set point value "lux"

The desired brightness setpoint value can be set via the lux 

potentiometer. The setting range is about 30 to 1000 lux. The 

factory presetting is 300 lux.

Brightness setpoint values from 30 to 3000 lux can be set via 

management remote control and app remote control.

Teach-in 

: When the lux potentiometer is moved to the 

teach-in position, the LED starts flashing for 20 seconds. 

As soon as the LED stops flashing, the currently measured 

brightness value is accepted as the new brightness setpoint 

value. When the teach-in position is quit, the set value on the 

LUX potentiometer is accepted as the new brightness setpoint 

value.

Teach-in can also be carried out using the remote controls 

"SendoPro 868-A", "theSenda P", or "theSenda B" (with 

"theSenda Plug app). In this case, the currently measured 

brightness value is immediately accepted as the new bright-

ness setpoint value.

The brightness measurement is deactivated at potentiometer 

setting "on". The light channel then switches only depending 

on presence.

Potentiometer - Lighting time delay

The following guidance values have proved themselves in 

practice and are recommended as settings:

 

Transit zones (no work area) approx. 5 min

 

Classroom                               approx. 10 min

 

Work areas (office, meeting room) approx. 10 min

 

 "Pulse": Control of staircase light timer switch (0.5 s 

"on" / 10 s "off")

Settings of switch contact H presence 

Potentiometer - Presence time delay

The contact closes if people are present and opens when the 

room is vacated after the time delay expires.

Potentiometer - Presence switch-on delay

 

The contact only closes when someone is present after 
expiry of the switch-on delay

 

0 = contact closes immediately if people are present

Parameters and control commands via remote 

control

The following parameters can be checked or changed via 

the remote control for support during start-up as well as 

servicing:

Parameter

Description

Can be 

que-

ried by 

SendoPro 

868-A/

theSenda 

B (app)

Can be 

chan-

ged by 

SendoPro 

868-A/

theSenda 

B (app)

Can be 

changed 

by the-

Senda P

Detection zone

Zone 1 / zone 2

x

x

Brightness set-

point value A

Value range in lux

x

x

x

Measurement off

x

x

x

Brightness 

actual value A

Query brightness 

actual value

x

Room correc-

tion factor A

Room correction 

factor

x

x

Brightness 

measurement 

value A

Lux meter brightness 

value in lux

x

Detection 

sensitivity

Detection sensitivity 

(PIR)

x

x

x

Time delay A

Value ranges in 

seconds/minutes

x

x

Pulse

x

x

Short presence 

A

On/Off

x

Time delay H

Value ranges in 

seconds/minutes

x

x

Switch-on 

delay H

Value ranges in 

seconds/minutes

x

Configuration 

type

auto/man

x

x

x

Control input S

auto/switch/push 

button S/push 

button O

x

Staircase light 

function

Off/On

x

x

Group address

All/I/II/III

x

x

LED display 

motion

Off/On

x

The parameters are sent to the presence detector via infrared 

by using the "SendoPro 868-A" management remote control, 

the "theSenda P" service remote control, or "theSenda B" app 

remote control (with "theSenda Plug" app). Changed parame

-

ters are immediately applied and used by the detector. 

With the "SendoPro 868-A" management remote control, as 

well as with "theSenda B" app remote control (with "the-

Senda Plug" app), parameters can be queried by sending 

values level-by-level to the detector. If the sent value is below 

the set parameter, the LED illuminates briefly. If the sent value 

is equal to or above the set parameter, the LED flickers for 2 

seconds.

Summary of Contents for thePassa P360-101 UP WH

Page 1: ... control theSenda B option and corres ponding app theSenda Plug iOS Android 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed persons under the guidance and supervision of a qualified electrician in accordance with the techni...

Page 2: ...ple are present or it is dark Channel H presence Channel H presence is used for HVAC control The switching response of the floating contact is influenced only by pre sence and not by brightness If the contact is closed the time delay will be restarted at every movement Push buttons or switches do not influence the contact Switch on delay The switch on delay prevents instantaneous switching on The ...

Page 3: ...ighting directly below the detector If the brightness measurement is deactivated chan nel A light only switches depending on presence brightness setpoint value set to on via potentiometer or set to mea surement off via remote control 1 8 m Suitable lamps The presence detector is designed for the operation of fluore scent compact fluorescent halogen and incandescent lamps as well as LEDs The maximu...

Page 4: ... L Light measurement only with the Master Parameters are only set on the Master Switch up to 10 detectors in parallel Use the phase with the same phase for all detectors Master thePassa P360 101 UP Slave thePassa P360 Slave UP Master Master parallel switching for several lighting groups Several Masters can be used in a parallel switching Each Master controls its lighting group according to its own...

Page 5: ... only closes when someone is present after expiry of the switch on delay 0 contact closes immediately if people are present Parameters and control commands via remote control The following parameters can be checked or changed via the remote control for support during start up as well as servicing Parameter Description Can be que ried by SendoPro 868 A theSenda B app Can be chan ged by SendoPro 868...

Page 6: ... the furniture With the room correction factor the brightness measurement value of lighting channel A is adjusted to the conditions in the room and in this way can be matched to the lux meter value measured at the surface beneath the presence detector Room correction factor Brightness value at the ceiling brightness value at the working surface Using management SendoPro 868 A remote control and lu...

Page 7: ...stable values 0 s no switch on delay 30 s 1 10 min Configuration type Fully automatic device The lighting is switched on and off automatically Due to presence absence and brightness SendoPro 868 A theSenda B app auto theSenda P Button A Semi automatic Lights must always be switched on manually Switching off occurs automatically by the presence detector due to absence or brightness SendoPro 868 A t...

Page 8: ...ment occurs the light and presence switch contacts close y y When no one is present the light switch contact opens after 10 s y y Brightness measurement deactivated detector does not react to brightness y y The detector reacts as in configuration type fully auto matic device even if semi automatic is set y y Teach in cannot be activated in test mode y y Test mode ends automatically after 10 min Th...

Page 9: ...e Flickering for 2 s The command sent from the remote control via infrared was accepted by the presence detector Lighting up briefly The command sent from the remote control via infrared was rejected by the presence detector The command is not valid Check the selected detector type or parameters on the SendoPro or in the app Fast flashing Error flashing The presence detector has found an error Fli...

Page 10: ...Details www theben de en theSenda B Item no 9070985 Details www theben de en theSenda S Item no 9070911 Details www theben de en 12 Contact Theben HTS AG Im Langhag 7b 8307 Effretikon SWITZERLAND Phone 41 52 355 17 00 Fax 41 52 355 17 01 Hotline Phone 41 52 355 17 27 hotline theben hts ch www theben hts ch All countries except Switzerland Theben AG Hohenbergstraße 32 72401 Haigerloch GERMANY Tel 4...

Reviews: