5
Setting of switch contact A light
Potentiometer - Brightness set point value "lux"
The desired brightness setpoint value can be set via the lux
potentiometer. The setting range is about 30 to 1000 lux. The
factory presetting is 300 lux.
Brightness setpoint values from 30 to 3000 lux can be set via
management remote control and app remote control.
Teach-in
: When the lux potentiometer is moved to the
teach-in position, the LED starts flashing for 20 seconds.
As soon as the LED stops flashing, the currently measured
brightness value is accepted as the new brightness setpoint
value. When the teach-in position is quit, the set value on the
LUX potentiometer is accepted as the new brightness setpoint
value.
Teach-in can also be carried out using the remote controls
"SendoPro 868-A", "theSenda P", or "theSenda B" (with
"theSenda Plug app). In this case, the currently measured
brightness value is immediately accepted as the new bright-
ness setpoint value.
The brightness measurement is deactivated at potentiometer
setting "on". The light channel then switches only depending
on presence.
Potentiometer - Lighting time delay
The following guidance values have proved themselves in
practice and are recommended as settings:
•
Transit zones (no work area) approx. 5 min
•
Classroom approx. 10 min
•
Work areas (office, meeting room) approx. 10 min
•
"Pulse": Control of staircase light timer switch (0.5 s
"on" / 10 s "off")
Settings of switch contact H presence
Potentiometer - Presence time delay
The contact closes if people are present and opens when the
room is vacated after the time delay expires.
Potentiometer - Presence switch-on delay
•
The contact only closes when someone is present after
expiry of the switch-on delay
•
0 = contact closes immediately if people are present
Parameters and control commands via remote
control
The following parameters can be checked or changed via
the remote control for support during start-up as well as
servicing:
Parameter
Description
Can be
que-
ried by
SendoPro
868-A/
theSenda
B (app)
Can be
chan-
ged by
SendoPro
868-A/
theSenda
B (app)
Can be
changed
by the-
Senda P
Detection zone
Zone 1 / zone 2
x
x
Brightness set-
point value A
Value range in lux
x
x
x
Measurement off
x
x
x
Brightness
actual value A
Query brightness
actual value
x
Room correc-
tion factor A
Room correction
factor
x
x
Brightness
measurement
value A
Lux meter brightness
value in lux
x
Detection
sensitivity
Detection sensitivity
(PIR)
x
x
x
Time delay A
Value ranges in
seconds/minutes
x
x
Pulse
x
x
Short presence
A
On/Off
x
Time delay H
Value ranges in
seconds/minutes
x
x
Switch-on
delay H
Value ranges in
seconds/minutes
x
Configuration
type
auto/man
x
x
x
Control input S
auto/switch/push
button S/push
button O
x
Staircase light
function
Off/On
x
x
Group address
All/I/II/III
x
x
LED display
motion
Off/On
x
The parameters are sent to the presence detector via infrared
by using the "SendoPro 868-A" management remote control,
the "theSenda P" service remote control, or "theSenda B" app
remote control (with "theSenda Plug" app). Changed parame
-
ters are immediately applied and used by the detector.
With the "SendoPro 868-A" management remote control, as
well as with "theSenda B" app remote control (with "the-
Senda Plug" app), parameters can be queried by sending
values level-by-level to the detector. If the sent value is below
the set parameter, the LED illuminates briefly. If the sent value
is equal to or above the set parameter, the LED flickers for 2
seconds.