7

remote control, the sensitivity can be decreased 

 or incre-

ased 

 by one increment each time the button is pushed.

Incre-

ment

Sensitivity

1

very insensitive

2

insensitive

3

Standard

4

sensitive

5

very sensitive

By selecting the test presence operating mode, the set sensi-

tivity increment is not changed.

Time delay channel A light

Value range

Adjustable values "SendoPro 868-A"/"theSenda B" (app)

10 s–60 min

Adjustable values "theSenda P"

10 s, 30 s, 60 s, 

2 min, 10 min, 

20 min, 60 min

Control for staircase light timer switch (0.5 s "on"/10 

s "off")
"SendoPro 868-A"/"theSenda B" (app)

Pulse

"theSenda P"

Button 

Short presence channel A light

The time delay of channel A light can be switched off sooner 

if a room is occupied only for a short time. (In fully automatic 

device and semi-automatic device configuration type)

The time delay is used according to the set parameter.

Off

If someone enters an unoccupied room and it is only occupied for 

up to 30 s, the light will be switched off prematurely after 2 min.

On

Time delay channel H presence

Channel H presence always switches in case of a presence, 

regardless of whether configuration type is set to fully auto

-

matic device or semi-automatic. The relay contact opens if the 

room is vacated only after the set time delay has expired.

Value range

Adjustable values "SendoPro 868-A"/"theSenda 

B" (app)

10 s – 120 min

Adjustable values "theSenda P"

10 s, 30 s, 60 s, 

2 min, 10 min, 

20 min, 120 min

Switch-on delay channel H presence

The relay contact only closes when someone is present after 

expiry of the set switch-on delay.

Value range

Adjustable values

0 s (no switch-on delay),

30 s, 1–10 min

Configuration type

Fully automatic device: The lighting is switched on and off 

automatically. (Due to presence/absence and brightness)

"SendoPro 868-A"/"theSenda B" (app)

auto

"theSenda P"

Button A

Semi-automatic: Lights must always be switched on manually. 

Switching off occurs automatically by the presence detector. 

(due to absence or brightness)
"SendoPro 868-A"/"theSenda B" (app)

man

"theSenda P"

Button  

Control input S

Control input S for manual switch on/off of channel A light 

automatically detects push buttons or switches.

Several push buttons can be connected to control input S.

¾

†

Use light push button only with neutral conductor 

connector.

Value range

Automatic detection of push button or switch. A signal that 

is present for less than 0.7 s is detected as a push button. 

Longer signals are evaluated as a switch.

 auto

To adapt to user behaviour, the type of 

the used signal transmitter can have 

a fixed setting. Automatic detection is 

deactivated.

When selecting the push button, ope-

ning contact or NO contact can also be 

specified.

Switch

Push button (NO 

contact)

Push button (ope-

ning contact)

  Switch

  Push button 

S

  Push button 

O

Staircase light function

The lighting can be switched on and off manually.

Off

The lighting can be switched on, but not switched 

off manually. It only switches off after the set time 

delay.

On

Group address

This parameter is applied when using the "theSenda S" user 

remote control.

A group address can be assigned to channel A light.

The group addresses can be programmed with the following 

remote controls:

Group address value range

Adjustable values "SendoPro 868-A"

I, II, III, All

Adjustable values "theSenda B"

I, II, III

Adjustable values "theSenda Plug"

I–VIII, All

Adjustable values "theSenda S"

I, II

Summary of Contents for thePassa P360-101 UP WH

Page 1: ... control theSenda B option and corres ponding app theSenda Plug iOS Android 2 Safety Danger of death through electric shock or fire Installation should only be carried out by a qualified electrician WARNING Work on electrical systems may only be carried out by qualified electricians or by instructed persons under the guidance and supervision of a qualified electrician in accordance with the techni...

Page 2: ...ple are present or it is dark Channel H presence Channel H presence is used for HVAC control The switching response of the floating contact is influenced only by pre sence and not by brightness If the contact is closed the time delay will be restarted at every movement Push buttons or switches do not influence the contact Switch on delay The switch on delay prevents instantaneous switching on The ...

Page 3: ...ighting directly below the detector If the brightness measurement is deactivated chan nel A light only switches depending on presence brightness setpoint value set to on via potentiometer or set to mea surement off via remote control 1 8 m Suitable lamps The presence detector is designed for the operation of fluore scent compact fluorescent halogen and incandescent lamps as well as LEDs The maximu...

Page 4: ... L Light measurement only with the Master Parameters are only set on the Master Switch up to 10 detectors in parallel Use the phase with the same phase for all detectors Master thePassa P360 101 UP Slave thePassa P360 Slave UP Master Master parallel switching for several lighting groups Several Masters can be used in a parallel switching Each Master controls its lighting group according to its own...

Page 5: ... only closes when someone is present after expiry of the switch on delay 0 contact closes immediately if people are present Parameters and control commands via remote control The following parameters can be checked or changed via the remote control for support during start up as well as servicing Parameter Description Can be que ried by SendoPro 868 A theSenda B app Can be chan ged by SendoPro 868...

Page 6: ... the furniture With the room correction factor the brightness measurement value of lighting channel A is adjusted to the conditions in the room and in this way can be matched to the lux meter value measured at the surface beneath the presence detector Room correction factor Brightness value at the ceiling brightness value at the working surface Using management SendoPro 868 A remote control and lu...

Page 7: ...stable values 0 s no switch on delay 30 s 1 10 min Configuration type Fully automatic device The lighting is switched on and off automatically Due to presence absence and brightness SendoPro 868 A theSenda B app auto theSenda P Button A Semi automatic Lights must always be switched on manually Switching off occurs automatically by the presence detector due to absence or brightness SendoPro 868 A t...

Page 8: ...ment occurs the light and presence switch contacts close y y When no one is present the light switch contact opens after 10 s y y Brightness measurement deactivated detector does not react to brightness y y The detector reacts as in configuration type fully auto matic device even if semi automatic is set y y Teach in cannot be activated in test mode y y Test mode ends automatically after 10 min Th...

Page 9: ...e Flickering for 2 s The command sent from the remote control via infrared was accepted by the presence detector Lighting up briefly The command sent from the remote control via infrared was rejected by the presence detector The command is not valid Check the selected detector type or parameters on the SendoPro or in the app Fast flashing Error flashing The presence detector has found an error Fli...

Page 10: ...Details www theben de en theSenda B Item no 9070985 Details www theben de en theSenda S Item no 9070911 Details www theben de en 12 Contact Theben HTS AG Im Langhag 7b 8307 Effretikon SWITZERLAND Phone 41 52 355 17 00 Fax 41 52 355 17 01 Hotline Phone 41 52 355 17 27 hotline theben hts ch www theben hts ch All countries except Switzerland Theben AG Hohenbergstraße 32 72401 Haigerloch GERMANY Tel 4...

Reviews: