6
Resetting the time switch
¾
Press the 4 buttons simultaneously.
▻
You can choose between RETAIN PROGRAM and DELETE
PROGRAM.
6. Technische Daten
Operating voltage:
230–240 V AC +10 % / –15 %
Frequency
50–60 Hz
Power consumption: max
0,4 W
Standby min
0,4 W
Max switching capacity.
16 A (at 250 V AC, cos
ϕ
= 1)
Switching capacity
4 A (at 250 V AC, cos
ϕ
= 0,6)
Min. switching capacity
10 mA/230 V AC
100mA/24 V AC/DC
Gap
<3 mm
Protection rating
IP 20 in accordance with
EN 60529
Protection class
II in accordance with
EN 60730-1 subject to
designated installation
Operating temperature
–25 °C … +55 °C
Power reserve
10 years at +20 °C
Rated impulse voltage
4 kV
Pollution degree
2
Contact
NO contact µ
Max. switching cycles with 16 A resistive
load
50 000
Incandescent lamp load
2000 W
Halogen lamp load
2000 W
Energy-saving lamp
300 W
Fluorescent lamps (LLB low-loss bal-
lasts):
uncorrected
series-corrected
parallel-corrected
2000 VA
2000 VA
1300 W (140 µF)
Fluorescent lamps (EB – electronic
ballasts)
1200 W
Mercury and sodium vapour lamps
parallel-compensated
730 VA (80 µF)
Compact fluorescent lamps (EB)
300 W
LED-lamps (<2 W)
55 W
LED-lamps (>2 W < 8 W)
180 W
LED-lamps (>8 W)
200 W
Contact material
tungsten prerun
contact
Switch output
phase independent
Corresponds to type 1 BSTU in
accordance with IEC/EN 60730-2-7 or
IEC/EN 60730-1
SELV switching is not permitted.
Switching of any external conductor is
permitted.
7. Contact
Theben AG
Hohenbergstr. 32
72401 Haigerloch
GERMANY
Tel. +49 7474 692-0
Fax ++49 7474 692-150
Hotline
Tel. +49 7474 692-369
Addresses, telephone numbers etc.
www.theben.de