118
8. Test-Mode
The PlanoCentro has two test modes.
●
Test presence, page 118
●
Test lighting, page 120
The test mode can only be started with voltage.
8.1 Test presence
The test presence serves to test presence detection and parallel switching.
The test presence can activated directly on the presence detector (without
power up) or with the SendoPro management remote control.
Activate
-
Push-button SW2; short button push 1x
-
"Test presence on" with the SendoPro management remote control
The test mode presence can always be activated.
Terminate
With subsequent restart:
-
Repress SW2 ends operation mode and restarts the detector.
-
Command "Test presence off" with the SendoPro management remote control
-
Power outage and thus power up
-
The detector automatically restarts after 10 minutes (see page 108)
Without restart:
-
Activation of test lighting with the SendoPro management remote control
LED display
Description
On
With movement (LED on) close channels A lighting and H presence.
Off
With absence (LED off) open both channels after 15 secs.