6.7 Switch-off delay time channel A Light
Value range
Adjustable values
10 sec .... 60 min
Self-learning switch-off delay time (normal energy saving mode) The switch-off delay time is
adjusted and if necessary increased according to user behaviour. The set value is not accepted.
between 2 .... 30min
switch-off delay time remain fixed
<=2 min. or >=30 min.
«Impulse»
I
: Control of staircase time switch
(0.5 sec "on“ / 9.5 sec "off“)
Impulse
Note:
Up to 2 min and above 30 minutes the switch-off delay time remains fix. The self-learning switch-
off delay time applies until the device is restarted, through switching the power off or a restart.
Practice values
Transfer zones
approx. 5min
Work stations
approx. 10min
6.8 Short presence channel A light
The switch-off delay time of channel A lighting can be switched off sooner when a room is only
occupied for a short time. (With function modes fully-automatic and semi-automatic)
The switch-off delay time is used according to set parameters.
Off
When entering an unoccupied room for a maximum of 30 seconds, the light switches off after two
minutes. The monitoring applies in combination with the self-learning switch-off delay time.
On