3
Setting the time delay (TIME 1)
If the motion detector detects no further movement, it swit-
ches off after the set time delay.
If you want to change the preset time
¾
Set the potentiometer to the desired time (5 s - 30 min).
If you want to use the pulse function (e.g. for a staircase light
timer switch)
¾
Set the potentiometer to
. The presence detector for
"staircase light timer switch" operation is on for 1 s and off
for
9 s.
Setting the HVAC time (TIME 2) (only LUXA 103-101 DE)
¾
Set the potentiometer to the desired time (10 s - 60 min.).
Setting the sensitivity (METRES)
You can reduce the sensitivity in order to avoid switching
errors.
¾
Set potentiometer METRES to the desired
sensitivity.
Manual operation
The lighting can
be manually switched on/off via a button.
L N
L
L‘
N R
N
L
When the light is on
¾
Briefly press button once (< 1 s)
▻
Light is off
When the light is off
¾
Briefly press button once
▻
The light is on for the time set on the potentiometer;
then the detector goes into automatic mode
Limiting the detection area
¾
Use the supplied cover clips to adjust the motion detector
to the desired detection area.
¾
Remove the required section of the cover clip by using
pliers or similar.
¾
Then
place it on the lens.
A
B
7. Technical data
Operating voltage
230 V AC ±10%
Frequency
50 Hz/60 Hz
Upstream protection device
10 A
Standby output
0.5 W
Switching capacity min.
10 mA
Protection rating
IP 44 (detector), IP 20 (power supply
unit) in accordance with EN 60529
Protection class
II
Operating temperature
0 °C … +45 °C
Brightness setting range
10 – 2000 lx/∞
Duty cycle range
LUXA 103-100: 5 s – 30 min for
lighting
LUXA 103-101: 5 s – 30 min for
lighting
10 s – 60 min for HVAC
Detection angle
360°
Detection area
lateral/frontal: 7 m/4 m
Installation height
2 – 3 m (2.5 m recommended)
Light switch output
µ contact 230 V AC, zero-cross
switching
Switch output HVAC (D1/D2)
LUXA 103-101: 5 A (at 250 V AC,
cos
ϕ
= 1) µ contact
Min. switching capacity
10 mA
Incandescent lamp load
max. 2000 W
Halogen lamp load
max. 2000 W
Low-voltage halogen lamps
(transformer)
max. 1000 VA
Fluorescent lamps (LLB low-loss
ballasts):
parallel compensated
max. 900 VA, 100 µF
Fluorescent lamps (EB – electronic
ballasts)
600 W
Compact fluorescent lamps (EB)
400 W
LED lamps (< 2 W)
35 W
LED lamps (> 2 W)
400 W