background image

3

Setting the time delay (TIME 1)

If the motion detector detects no further movement, it swit-

ches off after the set time delay.

 

If you want to change the preset time

¾

†

Set the potentiometer to the desired time (5 s - 30 min). 

 

 

If you want to use the pulse function (e.g. for a staircase light 

timer switch)

¾

†

Set the potentiometer to 

. The presence detector for 

"staircase light timer switch" operation is on for 1 s and off 

for  

9 s.

Setting the HVAC time (TIME 2) (only LUXA 103-101 DE)

¾

†

Set the potentiometer to the desired time (10 s - 60 min.). 

 

Setting the sensitivity (METRES)

You can reduce the sensitivity in order to avoid switching 

errors.

¾

†

Set potentiometer METRES to the desired  

sensitivity.

 

Manual operation

The lighting can

 be manually switched on/off via a button.

L N

L

L‘

N R

N

L

When the light is on

¾

†

Briefly press button once (< 1 s)

 

Light is off

When the light is off

¾

†

Briefly press button once 

 

The light is on for the time set on the potentiometer; 
then the detector goes into automatic mode

Limiting the detection area

¾

†

Use the supplied cover clips to adjust the motion detector 

to the desired detection area.

¾

†

Remove the required section of the cover clip by using 

pliers or similar.

¾

†

Then 

place it on the lens.

A

B

7.  Technical data

Operating voltage

230 V AC ±10%

Frequency

50 Hz/60 Hz

Upstream protection device

10 A

Standby output

0.5 W

Switching capacity min. 

10 mA

Protection rating 

IP 44 (detector), IP 20 (power supply 

unit) in accordance with EN 60529

Protection class 

II

Operating temperature 

0 °C … +45 °C

Brightness setting range

10 – 2000 lx/∞

Duty cycle range 

LUXA 103-100: 5 s – 30 min for 

lighting 

LUXA 103-101: 5 s – 30 min for 

lighting 

10 s – 60 min for HVAC

Detection angle

360°

Detection area

lateral/frontal: 7 m/4 m

Installation height

2 – 3 m (2.5 m recommended)

Light switch output

µ contact 230 V AC, zero-cross 

switching

Switch output HVAC (D1/D2)

LUXA 103-101: 5 A (at 250 V AC,  

cos 

ϕ

 = 1) µ contact

Min. switching capacity

10 mA

Incandescent lamp load

max. 2000 W

Halogen lamp load

max. 2000 W

Low-voltage halogen lamps 

(transformer)

max. 1000 VA

Fluorescent lamps (LLB low-loss 

ballasts): 

parallel compensated

 

max. 900 VA, 100 µF

Fluorescent lamps (EB – electronic 

ballasts)

600 W

Compact fluorescent lamps (EB) 

400 W 

LED lamps (< 2 W) 

35 W

LED lamps (> 2 W) 

400 W 

Reviews: