2
The device need
60 seconds to warm up.
Connecting the motion detector
Danger of death through electric shock or fire!
¾
¾
Installation should only be carried out by a
qualified electrician!
WARNING
¾
Disconnect power source
¾
Ensure device cannot be switched on
¾
Check absence of voltage
¾
Earth and bypass
¾
Cover or shield any adjacent live components
The warm-up phase takes approx. 60 s. The LED is perma
-
nently red.
L N
L
L‘
N R
N
L
L N
L
N R
D1
D2
N
L
L‘
LUXA 103-100 DE
LUXA 103-101 DE
Installation instructions and detection area
As the detector reacts to variations in temperature, avoid the
following situations:
¾
Do not direct motion detectors at objects with highly-
reflective surfaces such as mirrors, etc.
¾
Do not install the motion detector near heat sources, such
as heating outlets, air conditioning systems, lamps, etc.
¾
Do not direct the motion detector at objects that move in
the wind, such as curtains, large plants, etc.
¾
Pay attention to the direction of motion during the test run.
3,5 m
4 m
7 m
2 m
L
recommended installation height: 2.5 m
5. Walking test
The walking test is used to test the detection area.
¾
Set the time delay potentiometer (TIME 1) to
Test
. The
motion detector only reacts to movements, brightness
measurement is switched off.
¾
Walk through the detection area. Every detected movement
is indicated by the LED, and the light switch contact closes
for 2 s.
2 sec
Test
OPEN
20
30
10
6. Setting
The motion detector LUXA 103-100 DE has 3 potentiome-
ters for setting the time delay (TIME 1), brightness (LUX) and
sensitivity (METRES); with LUXA 103-101 DE the HVAC time
(TIME 2) can also be set.
LUXA 103-101 DE
Setting the brightness (LUX)
You can set different brightness values (LUX) with the
potentiometer.
If you want to change the preset brightness
¾
Set the potentiometer to the desired brightness
(10 – 2000 lux = )
If you want a specific brightness value to be learned using the
teach-in function
¾
At the desired brightness, set the potentiometer to
. The
LED flashes for 20 s, afterwards the measured brightness
value is accepted.
¾
Leave the potentiometer at position
.