6
Hour counter
The operating hours of the channel (relay) are displayed and
deleted in the OPTIONS menu. If the number of operating
hours exceeds the value set in the Service menu, SERVICE will
appear in the display.
Example: Replace a lamp after after 5,000 h.
¾
Delete operating hours or set a higher value in Service (e.g.
to 10,000 h)
Using the OBELISK top2 memory card
All functions can also be set on the PC using the OBELISK
software and transferred to the device via the memory card.
¾
Insert memory card in the time switch
¾
Read in/out saved switching times and device setups in
the time switch or start Obelisk program
¾
Remove memory card after copying etc.
!
Avoid mechanical overload and contamination during
storage/transport
L
PC software OBELISK top2 available at
www.theben.de
Copying OBELISK → TIME
This copies the switching program and optionally all time
switch settings (e.g. external input, time format etc.) from the
memory card in the time switch.
Copying TIME →OBELISK
This copies all switch programmes and settings from the time
switch to the memory card.
Starting OBELISK program
Takes on the switching times that are programmed on the
memory card.
As soon as the memory card is removed, the switching times
of the time switch are re-activated.
u
u
u
OBELISK
COPY
OBELISK ->
TSWI
COPY TSWI
-> OBELISK
RUN
OBELISK
CHECK
OBELISK
OVERWRITE
OK
OVERWRITE
OK
Resetting the time switch
¾
Press the 4 buttons simultaneously
▻
You can choose between KEEP PROGRAM and DELETE
PROGRAM
6. Technical data
Operating voltage:
12 - 24 V, +10 % / –15 %
12 - 24 V DC, +10 % / –15 %
Frequency:
50–60 Hz
Power consumption:
0,9 W - 1,3 W
Max switching capacity:
16 A (at 250 V, cos
ϕ
= 1)
switching capacity:
2 A (at 250 V, cos
ϕ
= 0,6)
Min. switching capacity:
10 mA/230 V AC
100 mA/ 24 V AC/DC
Shortest switching time:
1 second
Protection rating:
IP 20 in accordance with EN
60529
Protection class:
II in accordance with
EN 60730-1 subject to designa-
ted installation for supply with
FELV and/or mains switching
Protection class:
III for supply with SELV and
switching of SELV
Operating temperature:
–30 °C … +55 °C
Power reserve:
10 years at +20 °C
Time accuracy:
±0,25 s/day (25 °C)
Rated impulse withstand voltage:
4 kV
Pollution degree:
2
Contact:
two way switch
Glow lamp load (230 V):
1400 W
Halogen lamp load (230 V):
1400 W
Fluorescent lamp load: uncorrected
Series corrected:
parallel-corrected:
10000 VA
80 W (max. 12 µF)
Compact fluorescent tubes (EVG):
30 W
LED lamps (<2 W) (230 V):
6 W
LED lamps (>2 W < 8 W) (230 V):
20 W
LED lamps (> 8 W) (230 V):
20 W
Approved for switching SELV and mains
voltage.
7. Contact
Theben AG
Hohenbergstr. 32
72401 Haigerloch
GERMANY
Tel. +49 7474 692-0
Fax +49 7474 692-150
Hotline
Tel. +49 7474 692-369
Addresses, telephone numbers etc.
www.theben.de