7
Connection/installation of light sensor
!
Take length of connection cable into account: max. 100 m
(2 x 1.5 mm
2
), max. 50 m (2 x 0.75 mm
2
)
!
Avoid running sensor wiring parallel to mains power
cables
¾
Ensure correct polarity. Connect power source
Mounting light sensor 9070415
¾
Mounting light sensor: 0.5-2.5 mm
2
, strip cable by 9 mm
(max. 10 mm)
max. o 4 m m
Summary of Contents for 1110130