![The Armstrong Monitoring Corporation AMC-400 Series User Manual Download Page 46](http://html1.mh-extra.com/html/the-armstrong-monitoring-corporation/amc-400-series/amc-400-series_user-manual_1099482046.webp)
AMC-400 Series Digital Transmitter with Smart Sensor 2
42
9
APPENDIX: USER SUPPORTED MENU GUIDE
Below is the configuration menu that describes the USER supported portion
of the Digital Transmitter.
< is Pushbutton input; PB is pressed, SEL is selected.
> is LCD output; ___ is a Static Display, while ___ is Blinking Display
User Interface Action
Description
Comment
>411
Digital Series
2seconds
>S1A
Software Version Revision
Display (Version 1 Rev A)
2seconds
>0.08
Software Dot Revision
Display
2seconds
>H1C
Hardware Version Revision
Display (Version 1 Rev C)
2seconds
>___
Hardware Dot Revision
Display (___)
2seconds
>Ini
Unit Initialization
2seconds
>888
Unit Self-Test
1seconds
>Na
Sensor Not Available yet
Waiting for communication
from SS2 module.
7seconds
>co or no2 >PUP
>0.00
Scrolling Gas Concentration
Display;
Displays Sensor Unit if >1
unit present, Sensor gas,
Sensor Gas Concentration.
Running Display
<SEL >Co or n02 >PUP
>0.00
Exit Scrolling Gas
Concentration Display
Select Configuration
Menus
< PB >-CF
Configuration Title
Scroll to Choices
<SEL >A01
Front Bus Setup Choice
Select Front Bus
Configuration
< PB >-Fb
Front Bus Title
Scroll to Choices
<SEL >F01
MODBUS Address Choice
Select MODBUS
Address Configuration