Input Surge Protection
Protections
Approvals / Class
2.5KV Ring Wave,L-N 3KV/1.5KA
Battery Over Discharge Protection
Output Short Circuit Protection
RoHS, UL8750 Listed, UL924 Listed, CEC Title 20
1. Manual Diagnostic Mode:
Under the normal charging mode, after the battery is charged for 12 hours or fully
charged, long press the test button for 3S and hold it, enter the manual test mode, release
the button to exit the manual diagnostic mode.
2. Enable / Disable Self-Diagnostic Test System:
Under the Normal Charging Mode, press the button twice in two seconds, then press
the button longer than 2S and less than 5S, then press the button twice in succession, the
indicator light will be on and off for 5 times (1S interval), means disable the Self-Diagnostic
Test System successfully. If you want to enable the Self-Diagnostic Test System, repeat
the operation, the indicator light will be on and off for 3 times (1S interval), means “Enable”.
3. Enter Sleep Mode:
Under EM mode, press the test button 3S, the
Backup inverter
will enter Sleep
Mode(Storage and transportation),and activate it by connecting to AC power.
●
Solid Green ON
●
●
●
None LED OFF
●
Flashing Green, 1s on/1s off (cycle)
●
Slow Flashing Green, 5s on/5s off (cycle)
●
Flashing Green, 0.1s on/5s off (cycle)
Enable the Self-diagnostic test system.
Flashing Green,
1s on/1s off ( 5 times)
System OK/AC OK
.
System NG,battery voltage is too low
,
LED fixture is Short .
Battery not detected, check battery connection.
Discharge time is less than 90 minutes(Self-diagnostic test)
,
LED fixture is Open Circuit , Over Load .
EM working in Emergency mode.
Flashing Green,
1s on/1s off ( 3times)
Disable Self-diagnostic test system.
Dry, Damp Locations
4. Rest:
Under Error mode, press the test button 5S, the Backup inverter will Shutdown, and activate
it by connecting to AC power.
Ambient Operating Temperature Range
0°C to 50°C (32°F to 122°F)
In the normal charging mode, the system performs a monthly self-diagnostic test
every 30 days, the system switches to the emergency mode for 30S, and
automatically switches back to the normal charging mode after 30S.
Self-Diagnostic Test System
In the normal charging mode, the system switches to the emergency mode every
360 days (after 11 Months self-diagnostic test) and works until the end of
discharge. Automatically switches back to normal charging mode after discharge.
LED Indicators Status
THE BACKUP INVERTER Status/Mode
TEST SWITCH INDICATOR STATUS:
TEST SWITCH OPERATION: