Input Surge Protection
Protections

Approvals / Class

2.5KV Ring Wave,L-N 3KV/1.5KA
Battery Over Discharge Protection
Output Short Circuit Protection

RoHS, UL8750 Listed, UL924 Listed, CEC Title 20

1. Manual Diagnostic Mode:

 

     Under the normal charging mode, after the battery is charged for 12 hours or fully 

charged, long press the test button for 3S and hold it, enter the manual test mode, release 

the button to exit the manual diagnostic mode.

2. Enable / Disable Self-Diagnostic Test System:

     Under the Normal Charging Mode, press the button twice in two seconds, then press 

the button longer than 2S and less than 5S, then press the button twice in succession, the 

indicator light will be on and off for 5 times (1S interval), means disable the Self-Diagnostic 

Test System successfully. If you want to enable the Self-Diagnostic Test System, repeat 

the operation, the indicator light will be on and off for 3 times (1S interval),  means “Enable”.

3. Enter Sleep Mode:

    Under EM mode, press the test button 3S, the 

Backup inverter 

will enter Sleep 

Mode(Storage and transportation),and activate it by connecting to AC power.

Solid Green ON

None  LED OFF

Flashing Green, 1s on/1s off (cycle)

Slow Flashing Green, 5s on/5s off (cycle)

Flashing Green, 0.1s on/5s off (cycle)

Enable the Self-diagnostic test system.

Flashing Green,

1s on/1s off ( 5 times)

System OK/AC OK

.

System NG,battery voltage is too low

,

LED fixture is Short  .
Battery not detected, check battery connection.

Discharge time is less than 90 minutes(Self-diagnostic test)

LED fixture is Open Circuit , Over Load .

EM working in Emergency mode.

Flashing Green,

1s on/1s off ( 3times)

Disable Self-diagnostic test system.

Dry, Damp Locations

4. Rest:

   

Under Error mode, press the test button 5S, the Backup inverter will Shutdown, and activate

it by connecting to AC power.

Ambient Operating Temperature Range

0°C to 50°C (32°F to 122°F)

In the normal charging mode, the system performs a monthly self-diagnostic test 

every 30 days, the system switches to the emergency mode for 30S, and 

automatically switches back to the normal charging mode after 30S.

Self-Diagnostic Test System

In the normal charging mode, the system switches to the emergency mode every 

360 days (after 11 Months self-diagnostic test) and works until the end of 

discharge. Automatically switches back to normal charging mode after discharge.

LED Indicators Status

THE BACKUP INVERTER Status/Mode

TEST SWITCH INDICATOR STATUS:

TEST SWITCH OPERATION:

Summary of Contents for WP-CEP-12C-200VPE

Page 1: ...nel Do not use this emergency driver for other than intended use Not suitable for high risk task area lighting Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel IMPORTANT Indicator LED light illuminated indicates battery in charge mode when AC power is applied It is recommended and required by applicable code to te...

Page 2: ... luminaire manufacture This number will be given in lumens per watt lm w It is the installer s responsibility to validate the luminaire manufacturer s efficacy data This can be accomplished by direct measurement by review of independent 3rd party test data UL ETL etc accessing a public database of 3rd party data such as Design Lights Consortium www designlights org or other comparable means b Lume...

Page 3: ...n ON None LED OFF Flashing Green 1s on 1s off cycle Slow Flashing Green 5s on 5s off cycle Flashing Green 0 1s on 5s off cycle Enable the Self diagnostic test system Flashing Green 1s on 1s off 5 times System OK AC OK System NG battery voltage is too low LED fixture is Short Battery not detected check battery connection Discharge time is less than 90 minutes Self diagnostic test LED fixture is Ope...

Page 4: ...Wiring Diagram and Dimensions ...

Page 5: ......

Page 6: ... for typical installation and select appropriate mounting method Step 3 WIRING THE BACKUP INVERTER Use the wiring diagram found on page 4 as reference Connect the AC power source leads Switched and Unswitched to the input of the backup inverter Connect the output leads of backup inverter to the AC driver Wire the AC driver with the lamp in accordance with manufactures installation instructions Mak...

Page 7: ...Illustration 1 Illustration 2 ...

Reviews: