> Disconnect all power sources to the lighting fixture and ensure they are locked out during installation or
maintenance.
> The AC driver must be sourced from the backup inverter.
> Select a suitable location for the backup inverter and install such that its output leads can connect to
the input leads of the AC driver.
Step #1 Disconnect AC Power From Fixture
Step #2 INSTALL THE BACKUP INVERTER
> Select a suitable location on the ceiling for hangable device.
> Install the ring bolt to the backup inverter and fix it with screw.
> Install the hook to the backup inverter and fix it with screw.
> Open the cover of junction box .
> Install the Bushing (BN-M12-8, E492547, ZHEJIAN BANGNAI ELECTRIC CO LTD
Suitable for wire diameter 4-8mm
,
STYLE,SJTW,SJOW,SVT )
> Install the Bushing (BN-M18-10, E492547, ZHEJIAN BANGNAI ELECTRIC CO LTD
Suitable for wire diameter 6-10mm, SJTW,SJOW,STYLE, SVT )
> Hang the backup inverter to the hangable device on the ceiling.
> Hang the LED ligthing fixture to the hook of the backup inverter.
> Install the Bx cables on AC wires and dimming wires .
> See Illustration 1, for typical installation and select appropriate mounting method
Step #3 WIRING THE BACKUP INVERTER
> Use the wiring diagram found on page 4 as reference.
> Connect the AC power source leads (Switched and Unswitched) to the input of the backup inverter.
> Connect the output leads of backup inverter to the AC driver.
> Wire the AC driver with the lamp in accordance with manufactures installation instructions.
> Make sure all connections are in accordance with the National Electrical Code, Canadian Electrical Code
> In a readily visible location, attach the label “Caution -This Unit Has More Than One Power Connection
Point. To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers, Or Fuses And
DC Power Supply (Backup Inverter Connector) Before Servicing.”
and any local regulations.
Step #4 LOCK UP THE COVER OF JUCTION BOX & APPLY POWER
> After installation is complete, apply AC power .
> At this point, power should be connected to both the AC driver and the backup inverter, and the
Charging Indicator Light should illuminate indicating the battery is charging.
> A short-term discharge test may be conducted after the backup inverter has been charging for 1 hour.
Charge for 24 hours before conducting a long-term discharge test.