4.2.1 ADDITIONAL WIRE CLAMPS FOR EXTEND-A-GUN RC
For the Extend-A-Gun RC: Install the supplied wire clamps to the bottom of the lower wire skirt as shown in figures 4.2B and 4.2C. The
purpose of the additional wire clamps (if needed) is to give a known direction and anchor position to the wire for proper operation with
the Extend-A-Gun RC's wire anchor point. Length of wire from last clamp on the monitor to clamp on Extend-A-Gun to be 40 inches.
Wire should wrap 1 ½ times around Extend-A-Gun.
4.3 NOZZLE CONNECTION
The HURRICANE RC monitor outlet thread types are as shown in figure 3.3. The nozzle is simply screwed onto the Hurricane RC
monitor's exit threads. Insure that the nozzle's coupling does not make contact with the elevation drive housing when the monitor is in
its highest elevation position.
For nozzles with electric pattern control, a waterproof connector wire is provided at the bottom outlet of the Hurricane RC's control
station box. This wire attaches directly to TFT's electric Master 1250 nozzle. The electric actuator box of nozzle must be oriented to the
top side of nozzle for the connection wire to extend 90° above horizontal and 45° below elevation movement. (see figure 4.3 and refer to
Section 5.9 for properly attaching female to male connectors). Any other nozzle should have the corresponding male electrical
connector installed and long enough wire to extend 90° above horizontal and 45° below elevation movement of the nozzle.
DO NOT
CUT OFF THE FEMALE CONNECTOR ON THE MONITOR. THIS CONNECTOR IS MOLDED ONTO THE WIRE AND MUST
REMAIN ON TO MAINTAIN THE WATER TIGHTNESS OF THE ELECTRICAL SYSTEM.
FIG 4.3
Correct ER Nozzle Install Orientation
CAUTION
The nozzle threads must match the threads on the HURRICANE RC in both size and type.
Mismatched or damaged threads may cause the nozzle to leak or uncouple under pressure and
could cause injury.
CAUTION
Do not connect aluminum to brass or brass to aluminum. Dissimilar metals coupled together can
cause galvanic corrosion that will freeze the threaded joint or cause complete loss of thread
engagement. If dissimilar metals must be coupled together, the effects of corrosion can be greatly
delayed by various coatings on the metal such as powder paint, hard anodizing or silicone grease.
CAUTION:
CAUTION:
TFT's Master Stream 1250 ER Nozzle
TFT's Master Stream 1250 ER Nozzle
Electric Actuator Box must be on the Top
Electric Actuator Box must be on the Top
Side for its Edge to line up with Monitor
Side for its Edge to line up with Monitor
Waterway Top Body as shown.