INS467-9 38/47
Impaq Contact-W
The Impaq Contact-W has 3 additional inputs labelled MAG 1 COM MAG 2, these
inputs can be used for any N/C device. If the Reed switch is disabled the device can
be used as a transmitter for any device wired into one of the two inputs.
The two additional inputs are NOT independently programmable of the reed switch,
when mapped to a panel zone if either the reed switch or any of the inputs are
triggered the zone which the device is mapped too will go active.
Switch 3 on the expander controls how MAG 2/COM reports to the control panel.
By default the switch is OFF and anything connected to MAG 2/COM will report as a
tamper. When switch 3 is ON MAG 2/COM will report as alarm.
In the case of the Impaq Contact –W being used to trigger 24 hour circuits, or
where the zone is required to chime, ensure the device attributes are at the
default “Always Awake” as detailed in
The two additional inputs may also be used to transmit N/C signals from any other
locally powered or self-powered device, depending on the type of device used you
should choose the device attributes to suit.
7.3 Walktest Mode
Walktest Mode can be initiated from the Control Panel, Engineers Keypad,
RICOCHET Monitor or directly on the expander.
When in Walktest mode LED’s are enabled and the response time for devices
between activations is reduced to 10 seconds. Walktest will last for 1 hour.
Control Panel
Please refer to the Control Panel installation instructions to enter Walktest mode.
The countdown timer does NOT appear on the panel’s keypad.
Expander
Option switch 4 toggles Walktest mode on and off. To enable Walktest mode from
the expander switch Option switch 4 to the ON position. To leave Walktest mode