IMPORTANT INfORMATION AbOuT ThIs MANuAl
7
© TESVOLT We reserve the right to make technical changes. Version RD.TI.015.E.ENG_Installation_Manual_TS48V_v.C.01 Last revised 06/2020
1.4 LIMITATION OF LIABILITY
TESVOLT GmbH assumes no liability for personal injury, material damage, damage to the product or
consequential damage that is or was caused by failure to follow the instructions in this manual, inap-
propriate use of the product, repairs, opening of the cabinet and any other actions by unauthorized
and/or unqualified personnel on the product, or use of non-approved replacement parts.
Unauthorized modifications or technical changes to the product are forbidden.
1.5 APPROPRIATE USE
The TESVOLT TS 48 V is a modular battery storage system based on lithium-ion technology.
The TESVOLT TS 48 V is intended for use with the SMA Sunny Island battery inverter. Any other use
must be agreed with the Manufacturer and, if necessary, with the local energy supply company.
It may only be operated in closed rooms. The TESVOLT TS 48 V works in an ambient temperature
range of -10°C to 50°C and at a maximum humidity of 85%. The battery cabinet may not be exposed to
direct sunlight or placed directly beside sources of heat.
The battery cabinet may not be exposed to corrosive atmospheres.
When installing the battery storage system, ensure that it is standing on a sufficiently dry, horizontal
and flat surface with sufficient load-bearing capacity.
The altitude of the installation site may not be higher than 2000 m above sea level without approval in
writing from the manufacturer.
In regions subject to flooding, care must be taken to ensure that the battery cabinet is installed in a
suitably elevated location and is protected against contact with water.
According to IEC 62619, the storage system must be installed in a fire-proof room. This room must be
free from fire loads and must be equipped with an independent fire alarm unit in accordance with the
locally applicable regulations and standards. The room must be separated by at least Class T60 fire
doors.
Adherence to the specifications in this manual also forms part of appropriate use.
The TESVOLT TS 48 V may not be used:
•
for mobile use on land or in the air (it may only be used on water in agreement with, and with the
written consent of, the manufacturer),
•
for operating medical equipment,
•
as a UPS system.
1.6 GUARANTEE
The current guarantee conditions can be downloaded from the internet by visiting
www.tesvolt.com
.