background image

Electrical connection

8

Electrical connection

120V above ground

WARNING: Before commencing any electrical installation, always make sure that the 

electricity supply has been isolated at the main circuit breaker panel.

Note: 

The following connection details described here are primarily used in North America.

To access the electrical connections, open 

the enclosure by removing the two screws 
on the left-hand side using a T15 Torx L 
driver. Then unhook the latch located on 
the bottom of the unit (over the cable 
holder).

Caution: Before connecting any 

wires, make sure you have identified 

the type of utility service connection 
available. For more information, refer to 

Utility service connections, page 4

ClipperCreek, Inc.

READY

CHARGE

PROTECT

SERVICE

VEHICLE
GROUND

TERMINAL

L1

L2

GND

CONTACTOR

Service Side

Vehicle Side

Note:

The Home Connector requires a 

dedicated 208/240 VAC 60 Hz, 
single-phase circuit, with its own 90A 
circuit breaker.

Do not use a GFCI breaker. The Home 
Connector contains a Personal 
Protection circuit specifically designed 
for use with electric vehicles.

Only 3 wires are required (L1, L2 and 

GND), as shown in the illustration. 

For branch circuits of 90A, use 4 AWG, 
75°C copper wire. For installations less 
than 90A, use conductors sized 
according to Table 310.16 of NEC, or in 
accordance with local electrical codes.

The two phases (L1 and L2) are 

terminated on the input side of the 
CONTACTOR. The ground (GND) is 
terminated on the Ground Terminal at 
the bottom of the enclosure.

Be careful not to damage the PC Board 
when removing the power entry 
knock-out, attaching the conduit, or 
when wiring the service conductors to 
the contactor.

Installation is complete. Before securing 
the enclosure, perform the 
post-installation testing procedure 
described on page 10.

Home Connector Users Manual.book  Page 8  Monday, April 26, 2010  12:38 PM

Summary of Contents for HOME CONNECTOR

Page 1: ...ClipperCreek Inc Users Manual HOME CONNECTOR Home Connector Users Manual book Page 1 Monday April 26 2010 12 38 PM...

Page 2: ...ions 120V above ground 4 230V above ground 6 Installation Installing the Home Connector 7 Electrical connection 120V above ground 8 230V above ground 9 Post installation testing Confirming a successfu...

Page 3: ...ped over or subjected to damage or stress Environmental considerations At the end of its life this product should be recycled according to local laws and regulations Contact Tesla Motors for recycling...

Page 4: ...nature of the failure see Front panel indicator lights page 11 This feature helps to ensure that your vehicle will be charged and ready for use when needed Temporary problems such as ground faults or...

Page 5: ...wiring 230V above ground 230V AC single phase LINE NEUTRAL and EARTH Current and frequency 90A Circuit Breaker The maximum current for the vehicle is 70A At 240V this will be 17 kW maximum At 230V thi...

Page 6: ...the Neutral at the service to earth ground Ground fault protection is not possible unless the Neutral center tap on the service transformer is connected to an earth ground If ground is not provided by...

Page 7: ...ust each measure 120V to neutral Consult the transformer manufacturer s literature to verify that the single leg can supply the required power Caution Do not use a 3 phase delta connected transformer...

Page 8: ...ectly connected and labeled The illustration provided on this page shows the most commonly used wiring format in Europe Note The LINE NEUTRAL and EARTH outputs on the following illustration correspond...

Page 9: ...ide an adequate mounting surface 2 Attach the Home Connector to the wall studs using four 1 4 x 2 1 2 M6 lag screws The length of the screws must be adequate to securely anchor the Home Connector If m...

Page 10: ...e The Home Connector requires a dedicated 208 240 VAC 60 Hz single phase circuit with its own 90A circuit breaker Do not use a GFCI breaker The Home Connector contains a Personal Protection circuit sp...

Page 11: ...cle Side Note The Home Connector requires a dedicated 230 VAC 50Hz single phase circuit with its own 90A circuit breaker Do not use a GFCI breaker The Home Connector contains a Personal Protection cir...

Page 12: ...loses and the amber CHARGING light illuminates If a vehicle is available connect the Home Connector to the vehicle and verify that the contactor closes and the amber CHARGING light illuminates Once a...

Page 13: ...anel indicator lights GREEN READY LIGHT AMBER CHARGING LIGHT RED PROTECTION LIGHT RED SERVICE LIGHT CONDITION OFF OFF OFF OFF No service power ON OFF OFF OFF Home Connector has power but the vehicle i...

Page 14: ...emains illuminated unplug the vehicle If the red light goes out plug the vehicle back in and see if charging begins normally If charging does not begin normally and the red PROTECTION or SERVICE light...

Page 15: ...use cleaning solvents scouring powder or any type of abrasive pad to clean the Home Connector its charging cable or the vehicle s charging port WARNING To reduce the risk of electrical shock or equip...

Page 16: ...been detected follow these steps 1 Unplug the vehicle 2 Inspect the connector and the vehicle s charge port to verify they are clean and undamaged If necessary remove any accumulation of dust or dirt...

Page 17: ...TESLAMOTORS COM Home Connector Users Manual book Page 2 Monday April 26 2010 12 38 PM...

Reviews: