31
VI. TECHNICAL SPECIFICATIONS
MODEL
CL115D
Output (VA)
15000
Output (KW)
10500
Output Power Factor
0.7
INPUT
Number of Phases
1 phase + neutral
Input Voltage
220/230/240 VAC (3 wire)
Input Voltage Range
(without switching to battery power)
170-275V adjustable
Input Power Factor (PF)
>0.99 at full load
Input THDI
<5% at full load
Input Frequency
50 Hz nominal
Input frequency tolerance
40-65 Hz
By-pass Voltage
220/230/240 VAC, +/-10% (adjustable)
By-pass Frequency
50 Hz
By-pass Frequency Tolerance
(for synchronization)
Adjustable b/- 1.0 and 3.0 Hz
RFI Level
EN62040
Split By-pass Connection
OPTIONAL
Input power connections
Hardwired from the rear
Maintenance bypass switch
OPTIONAL
OUTPUT
Number of phases
1 phase + n earth (3 wire)
Output Voltage
220/230/240 VAC (3 wire) user selectable
Output Voltage Tolerance
+/- 1%
Output Frequency
50 Hz
Output Frequency Tolerance (line synchronous)
Adjustable b/-1.0 and 3.0 Hz
Output Frequency Tolerance (free running)
0.01%
Load Crest Factor
3:1
Output Voltage THD
<3%
Overload
Less than 100% continuous
100%-125% for 10 minutes (adjustable)
126%-150% for 1 minute (adjustable)
Output connections
Ha2Xiec sockets on the rear side
Weight
41 kgs
Summary of Contents for CL115D Series
Page 1: ...UPS USER MANUAL CL115D...
Page 4: ...AGKK9530 01 2011...
Page 37: ...33...