IP.HIGH:BATT /MESSAGE (During mains high alarm operate from batteries or not selection)
OPTION
DESCRIPTION
BATT
During A65 mains high alarm, UPS starts operating from batteries (for protection)
MESSAGE
During A65 mains high alarm, UPS shows only message
In some cases, if the mains input voltage is high (adjustable level), it is better to operate on batteries to prevent
any possible damage to the UPS.. But this selection can cause battery discharge if the mains input voltage is
continuously high. This function is selectable from adjust menu.
Optional dry contact AUX relays function selection from ADJUST MENU
Two auxiliary relays are available with selectable functions from the adjust menu. The selectable functions are
as follows:
Message
Function
RLX:COMMON ALARM
Relay activates on any alarm
RLX:BT.OUT.TOLER
Relay activates if battery voltage is out of tolerance
RLX:OP.OUT.TOLER
Relay activates if output voltage is out of tolerance
RLX:IP.OUT.TOLER
Relay activates if input voltage is out of tolerance
RLX:BYPASS
Relay activates if load is transferred to bypass
RLX:MAINS OK
Relay activates if input voltage is restored
RLX:OVERLOAD
Relay activates if load is greater than 100%
RLX:BATT TEST
Relay activates if battery test is being performed
RLX:OVERTEMP.
Relay activates if cabinet inside temperature is high
RLX:BATT.FUSE
Relay activates if battery fuse is off or blown
RLX:BATT.BAD
Relay activates if battery test fails
RLX:BOOST CHARGE
Relay activates if boost charge is active
RLX:OUTPUT OFF
Relay activates if the output voltage is zero
RLX:INV.FAILURE
Relay activates if inverter failure alarm occurs
RLX:SHUTDOWN
Relay activates if shutdown is applied
RLX:FAULT
Relay activates if any fault occurs
Some other features in adjust menu:
Function
Mains voltage low alarm level
Adjustable
Mains voltage OK level
Adjustable
Mains voltage high alarm level
Adjustable
Bypass input voltage high warning level
Adjustable
Bypass input voltage low warning level
Adjustable
Battery voltage high alarm level
Adjustable
Battery voltage low warning level
Adjustable
Battery voltage shutdown level
Adjustable
Battery test failed voltage level
Adjustable
Cabinet temperature high alarm level
Adjustable
Output voltage high alarm level
Adjustable
Output voltage low alarm level
Adjustable
Battery charge current
Adjustable
Battery quantity selection
Adjustable
Frequency synchron band
Adjustable
Boost charge time
Adjustable
Voltage range selection
220-230 volts AC selectable