TECHNICAL SPECIFICATIONS
MODELS
Unit ECS 600 ECS 700 ECS 800 ECS 900 ECS 1000
Heat power
kcal/h 600.000 700.000 800.000 900.000 1.000.000
kW
697,3
813,6
929,8
1046
1162,2
Heat input
kcal/h 659.300 769.200 879.100 989.000 1.099.000
kW
766,3
894
1021,7
1149,4
1277,3
Max. Operating Temperature
o
C
105
105
105
105
105
Temperature control range
o
C
30-90
30-90
30-90
30-90
30-90
Firing chamber pressure
mbar
5,3
5,9
6,4
7
7,5
Max. Operating pressure
bar
5
5
5
5
5
Test Pressure
bar
7,5
7,5
7,5
7,5
7,5
Boiler water capacity
lt
846
969
1232
1306
1446
Shaft diameter
mm
300
300
350
350
350
Firing chamber dimensions
738
738
820
820
820
L
1583
1853
1776
2015
2265
Input-Output Water
Connections
Inch
3"
3"
4"
4"
4"
Shaft exit temperature range
o
C
175-195 175-195 175-195 175-195
175-195