November 2006
26
RL4000
Light
Tower
Part
No.
833005
Rev
A
TROUBLESHOOTING
TROUBLE
POSSIBLE
CAUSE
REMEDY
6.Engine runs but produces a
a.Crankcase oil level is too high
a.Drain oil to its proper level
dense smoke
b.Low compression
b.Have a trained mechanic
inspect for broken or seized
rings. Inspect valve clearances
7.Engine overheats
a.Blocked cooling air intakes
a.Inspect the front and rear intakes
and clear as needed
b.Low coolant levels
b.Replace the coolant with a 50%
water/coolant solution
c.Radiator fins have become
c.Clear the radiator fins
clogged
d.Fan belt is loose
d.Tighten fan belt
8.Engine runs but the battery
a.Alternator has failed
a.Have a trained mechanic inspect
voltage
is
low
the
alternator
9.Engine runs but the light will
a.Circuit breakers are tripped
a.Reset the circuit breaker
not operate
b.Loose connections in the wiring
b.Have a trained electrician inspect
system
the ballast box wiring system
c.Burned out bulb
c.Replace the bulbs as needed
d.Defective capacitor
d.Have a trained electrician inspect
(Leroy Somers Generator)
the capacitor
e.Defective AC generator
e.Have a trained electrician inspect
the generator
f.Engine speed is too low
f.Have a trained mechanic inspect
the engine speed and reset to
1800rpm @ 60hz
g.Defective ballast and capacitors
g.Have a trained electrician inspect
the ballast and capacitors
10.Unusual noise coming from
a.The generator has a defective
a.Have a trained electrician inspect
the generator
bearing or damaged fan blade
the generator
11.Lamp will not start
a.Lamp loose in socket
a.Inspect lamp base to see if there
is arcing at center contact button.
Tighten lamp. Check socket for
damage. Replace if needed.
b.Floodlight plugs not tight
c.Defective ballast
c.Interchange ballast plugs. If lamp
starts, replace ballast. Check for
swollen capacitors, charred wiring,
core and coil, or other signs of
excessive heat.
d.Low voltage
d.Check line voltage at ballast input.
Voltage should be within 10% of
b.Check plug and receptacle. Tighten
if needed
rating when operating at normal load.
Increase supply voltage or remove
external load.
Summary of Contents for RL4000D2
Page 23: ...November2006 22 RL4000LightTower Part No 833005 Rev A SPECIFICATIONS DIMENSIONS...
Page 34: ...November2006 Part No 833005 Rev A RL4000LightTower 33 MODEL NUMBER IDENTIFICATION...
Page 38: ...November 2006 Part No 833005 Rev A RL4000 Light Tower 37 Wiring Diagrams Section...
Page 39: ...November 2006 38 RL4000 Light Tower Part No 833005 Rev A Fixture Wiring Diagram...
Page 40: ...November 2006 Part No 833005 Rev A RL4000 Light Tower 39 1000MH Ballast Diagram...
Page 41: ...November 2006 40 RL4000 Light Tower Part No 833005 Rev A 1000HPS Ballast Diagram...
Page 42: ...November 2006 Part No 833005 Rev A RL4000 Light Tower 41 AC Wiring For A Light Tower Diagram...
Page 43: ...November 2006 42 RL4000 Light Tower Part No 833005 Rev A DC Engine Wiring Diagram...
Page 44: ...November 2006 Part No 833005 Rev A RL4000 Light Tower 43 Consolidated Coil Cord With Plug End...
Page 45: ...November 2006 44 RL4000 Light Tower Part No 833005 Rev A This page intentionally left blank...
Page 46: ...November 2006 Part No 833005 Rev A RL4000 Light Tower 45 Parts Catalog Section...
Page 49: ...November 2006 48 RL4000 Light Tower Part No 833005 Rev A This page intentionally left blank...
Page 51: ...November 2006 50 RL4000 Light Tower Part No 833005 Rev A FRAME ASSEMBLY...
Page 53: ...November 2006 52 RL4000 Light Tower Part No 833005 Rev A CABINET ASSEMBLY...
Page 61: ...November 2006 60 RL4000 Light Tower Part No 833005 Rev A FIXTURE ASSEMBLY...