5 - 16
DPL-25S • DPL-30S • DPL-35S Super Series
Part No. 40462
September 2016
Section 5 - Troubleshooting Flow Charts
CHART 6
Continued from the
previous page.
While pushing in and
holding the control
activate switch, check for
power at terminal 4 of the
up switch contact.
Replace the red wire
(because of open circuit)
between the control
activate switch contact
block and the up switch
contact block.
While pushing in the
control activate switch
and activating the up
function, hold both
switches and check for
power at terminal 3 of the
up switch contact.
Replace the up switch
N.O. contact block.
While pushing in the
control activate switch
and activating the up
function, hold both
switches and check for
power at terminal 13
(orange wire) of the 13
pole terminal strip (J1) in
the ground control box.
Replace the 16/6 cable
because of open in the
orange wire OR repair
open in the quick
disconnect under ground
control box.
12V DC
0V DC
0V DC
12V DC
0V DC
While pushing in the
control activate switch
and activating the up
function, hold both
switches and check for
power at terminal 11
(white wire) of the 13 pole
terminal strip (J1) in the
ground control box.
12V DC
0V DC
Replace P.C. board OR
consult Genie Industries
service Department.
12V DC
Continued on the next
page.