7
Other Accessories
OCR checker, type ANU-1
The OCR checker allows easy checking of the long time-delay trip,
short time-delay trip, instantaneous trip, ground fault trip functions
and the pre-trip alarm function of the OCR in the field.
¡
Ratings and specifications
Power supply
• AC100–110V, 50/60Hz
or
AC100–240V, 50/60Hz with type C plug
• 4
~
AA alkaline cells
Power consumption
7VA
Dimensions
101 (W)
~
195 (H)
~
44 (D) mm
Weight
400 g
Current transformer for neutral line (separate type)
When using a 3-pole ACB with the ground fault protection function to protect a 3-phase, 4-wire system against ground fault, install
an appropriate current transformer (CT) to the neutral line of the system.
TERASAKI can provide this neutral line CT as an option.
For the 4-pole ACB, a measuring CT instead of the neutral line CT is already built into the neutral phase of the ACB when the
ground fault protection is fitted.
Specifications
4
Type
CW80-40LS
200
1250
400
1600
800
Rated secondary current is 5A
Rated
Primary
Current (A)
Type
EC160-40LS
1600
3200
2000
4000
2500
Rated secondary current is 5A
Rated
Primary
Current (A)
• Outline dimension of CT for neutral line
AR208S, AR212S, AR216S
AR212H, AR216H, AR316H
AR220S, AR325S, AR332S, AR440S
AR220H, AR320H, AR325H, AR332H
Contact Terasaki for how to check the reverse power trip function.
The over-current trip device of
TemPower2
provides a ground fault protection on the line side (optional) as well as on the load side
as shown above. When the ACB is used for protection of a 3-pole, 4-wire system, select the same current transformer for the neutral
line shown above.