63
62
Technical Data
7
Dielectric strength
Type
AR208S
AR212S
AR216S
AR220S
AR325S
AR332S
AR440S
Rated current (A)
800
1250
1600
2000
2500
3200
4000
DC internal resistance per pole (m
1
)
0.033
0.033
0.028
0.024
0.014
0.014
0.014
AC power consumption for 3 poles (W)
200
350
350
490
600
780
1060
Internal resistance and power consumption
Circuit
Withstand voltage (at 50/60 Hz)
Main circuit
Between terminals,
AC3500V for 1 minute
12kV
terminal group to earth
Auxiliary switches
For general service
Terminal group to earth
AC2500V for 1 minute
6kV
For microload
Terminal group to earth
AC2000V for 1 minute
4kV
Position switches
Terminal group to earth
AC2000V for 1 minute
4kV
Over-current release (OCR)
Terminal group to earth
AC2000V for 1 minute
4kV
Power supply for undervoltage/
Terminal group to earth
AC2500V for 1 minute
6kV
reverse power trip function
Other accessories
Terminal group to earth
AC2000V for 1 minute
4kV
Note: The values shown above are those measured on phase connections and cannot be applied to control terminals on the ACB.
Rated Impulse withstand
voltage
U
imp
Derating
Control circuits
Based
Ambient
Type
AR208S
AR212S
AR216S
AR220S
AR325S
AR332S
AR440S
Standards
temperature
Connecting
2
~
50
~
5t
2
~
80
~
5t
2
~
100
~
5t
3
~
100
~
5t
2
~
100
~
10t 3
~
100
~
10t
4
~
150
~
6t
(°C)
bar sizes
IEC60947-2
40 (Standard ambient
800
1250
1600
2000
2500
3200
4000
EN 60947-2
temperature)
AS3947.2
45
800
1250
1600
2000
2500
3200
4000
50
800
1250
1600
2000
2500
3200
4000
55
800
1200
1540
1820
2500
2990
3940
60
800
1150
1460
1740
2400
2850
3760
NEMA, SG-3
40 (Standard ambient
800
1250
1540
2000
2500
3200
3700
ANSI C37.13
temperature)
45
800
1190
1470
1960
2500
3010
3580
50
800
1130
1390
1860
2440
2860
3470
55
790
1070
1310
1750
2300
2690
3350
60
740
1000
1230
1640
2150
2520
3140
JIS C8372
40 (Standard ambient
800
1250
1600
2000
2500
3200
3700
temperature)
45
800
1250
1600
1900
2500
2900
3580
50
800
1190
1540
1820
2500
2800
3470
55
800
1130
1460
1740
2400
2710
3350
60
800
1080
1390
1650
2280
2610
3230
Note: The values are applicable for both Draw-out type and Fixed type.
The values of AR208S, AR212S and AR216S are for horizontal terminals on both line and load side.
The values of AR220S, AR325S, AR332S and AR440S are for vertical terminals on both line and load side.
Above figures are subject to the design of the enclosure and rating of busbar.
• Standard Series
• Standard Series
Type
AR212H
AR216H
AR220H
AR316H
AR320H
AR325H
AR332H
Rated current (A)
1250
1600
2000
1600
2000
2500
3200
DC internal resistance per pole (m
1
)
0.024
0.024
0.024
0.014
0.014
0.014
0.014
AC power consumption for 3 poles (W)
260
350
490
310
430
600
780
• High fault Series
Based
Ambient
Type
AR212H
AR216H
AR220H
AR316H
AR320H
AR325H
AR332H
Standards
temperature
Connecting
2
~
80
~
5t
2
~
100
~
5t
3
~
100
~
5t
2
~
100
~
5t
3
~
100
~
5t
2
~
100
~
10t
3
~
100
~
10t
(°C)
bar sizes
IEC60947-2
40 (Standard ambient
1250
1600
2000
1600
2000
2500
3200
EN 60947-2
temperature)
AS3947.2
45
1250
1600
2000
1600
2000
2500
3200
50
1250
1600
2000
1600
2000
2500
3200
55
1250
1600
1820
1600
2000
2500
2990
60
1250
1550
1740
1600
2000
2400
2850
NEMA, SG-3
40 (Standard ambient
¶
1600
2000
¶
¶
2500
3200
ANSI C37.13
temperature)
45
¶
1600
1960
¶
¶
2500
3010
50
¶
1600
1860
¶
¶
2440
2860
55
¶
1510
1750
¶
¶
2300
2690
60
¶
1420
1640
¶
¶
2150
2520
JIS C8372
40 (Standard ambient
1250
1600
2000
1600
2000
2500
3200
temperature)
45
1250
1600
1900
1600
2000
2500
2900
50
1250
1600
1820
1600
2000
2500
2800
55
1250
1550
1740
1600
2000
2400
2710
60
1250
1480
1650
1600
1900
2280
2610
Note: The values are for vertical terminals on both line and load side.
Above figures are subject to the design of the enclosure and rating of busbar.
¶
: Contact Terasaki for details.
• High fault Series
3P
4P
3P
4P
3P
4P
3P
4P
3P
4P
Draw-Out Body (Kg)
45
51
46
52
46
52
56
68
71
92
Draw-Out Chassis (Kg)
28
35
30
38
33
42
49
57
68
84
Total Draw-Out Weight (Kg)
73
86
76
90
79
94
105
125
139
176
Fixed (Kg)
53
59
54
60
54
60
80
92
Weight
Type
AR208S~212S
AR216S
AR220S
AR325S~332S
AR440S
AR212H~220H
AR316H~332H
Note: The above weights are based on normal specifications with the OCR and standard accessories