KRB-5200h
-11-
3.3.3 Auxiliary Switch (AX) and Alarm Switch (AL)
The auxiliary switch is used to indicate the ON or OFF state of the ACB.
The alarm switch (optional) is used to indicate the TRIPPED state of the ACB.
Switch Operation
Contact arrangement
State of ACB
ON
OFF
TRIPPED
AX AXb AXa
AXc
AXc - AXa
Close
Open
AXc - AXb
Open
Close
AL ALb1 ALa1
ALc1
ALc1 - ALa1
Open
Close
ALc1 - ALb1
Close
Open
1) Connection
Connect the control wire to the auxiliary terminal.
For the rear-connected ACB, connect the control wire to the specified terminal on the right side of
the ACB.
For the plug-in ACB, connect the power supply wire to the specified terminal on the rear side of
the mounting base.
2) Contact ratings
Caution : The contact load must fall within the range from the minim load to the rated load.
Caution : The ratings shown on the accessory nameplate are for the resistive/inductive load.
For lamp or motor load, see the following table.
(The lamp load involves an inrush current of 10 times the rated load. The inductive load has a
power factor of 0.4 (AC) and a time constant of 7 ms (DC). The motor load involves an inrush
current of 6 times the rated load.)
Applied current
(at 50/60 Hz)
Current (A)
Minimum
load
Resistive load
Lamp load
Inductive load
Motor load
480 VAC
1
0.2
1
0.3
250 VAC
5
1.5
5
2
30 VDC
125 VAC
5
2
5
3
26.7 mA,
250 VDC
0.3
0.05
0.3
0.05
5 VDC
125 VDC
0.6
0.1
0.6
0.1
150 mA
30 VDC
5
3
4
3