9.  Factory default settings

 

Disconnect the sensor from the bus (switch off the power supply). 

 

Press and hold “config” button. Don’t release the button, connecting the sensor to the bus 

(switch on the power supply). 

 

The “status” LED will be ON for 3 seconds and after this will flash for 7 seconds. After the 10-th 

second the LED will be ON.

 

Release the button. The sensor will restart with factory default settings.

10.  Firmware update

 

The firmware of the sensor can be updated with Teracom controller which supports 

 

MODBUS RTU or MBRTU-Config software. For more details ask your dealer.

11.  Modbus address table

Register name

R/W

FC

PDU

Address

(Decimal)

Logical 

address 

(Decimal)

Offset 

(Decimal

Data size

Default

Valid values

RS-485 address

R/W

03/06 10

40011

40001

16-bit Integer 1

1-247

Baud rate *

R/W

03/06 11

40012

40001

16-bit Integer 19200

2400, 4800, 9600, 

19200, 38400, 57600

Parity, data, stop 

bits *

R/W

03/06 12

40013

40001

16-bit Integer 1

1=E81, 2=O81, 3=N81

Bytes order

R/W

03/06 13

40014

40001

16-bit Integer 1

1= MSW, LSW 

2= LSW, MSW

Temperature  

(Measured)

R

03

100

40101

40001

32-bit Float 

Temperature  

Dimension 

R

03

104

40105

40001

4 bytes UTF-8

ID 64-49 bits

R

03

108

40109

40001

16-bit Integer

ID 48-33 bits

R

03

109

40110

40001

16-bit Integer

ID 32-17 bits

R

03

110

40111

40001

16-bit Integer

ID 16-1 bits

R

03

111

40112

40001

16-bit Integer

Sub-family number

R

03

112

40113

40001

16-bit Integer

FW version

R

03

113

40114

40001

16-bit Integer

Vendor URL

R

03

300

40301

40001

64 bytes UTF-8 

teracomsystems.com

Test value (floating 

point, MSW first)

R

03

332

40333

40001

32-bit Float 

-9.9(0xC11E6666)

LSW - Least significant word (bits 15 … 0);
MSW - Most significant word (bits 31 … 16)
PDU address - Actual address bytes used in a Modbus Protocol Data unit
A “NaN” value is returned for unavailable floating-point values (e.g. in case of measurement error)
*  The settings will take effect after restart of the sensor by power on reset.

 