out setting on the adjustable low pressure switch without adding glycol to the circulating
system. Evaporator damage will result and this damage is not covered by the factory
warranty.
G.
If your unit is equipped with a non-adjustable “fixed” pressure switch with a factory low
limit of 48°F this switch must be replaced with a switch with a lower limit. The lower range
low pressure switch can be obtained from the factory by calling 317-887-0729 and asking
for the service department. The model and serial number of your unit is required. A
qualified refrigeration technician is required to change the switch though no gas recovery
is required. The switch attaches to a threaded fitting on the refrigeration line.