INSTALLATION INSTRUCTIONS
Gas Furnace: (F/G)MAC
12
440 01 4201 01
Specifications subject to change without notice.
Figure 8
Unconverted Factory Configuration as viewed in the Downflow orientation
Remove relief tube from relief
port on condensate trap.
Remove pressure switch tube from
front of pressure switch.
Remove trap from
collector box.
Loosen clamp on inlet
to vent elbow.
Remove middle and bottom plugs.
DO NOT DISCARD.
Remove tube from
relief port.
Representative drawing only, some models may vary in appearance.
Downflow Trap Configuration
A11277
Representative drawing only, some models may vary in appearance.
Condensate Trap
−
Horizontal
Orientation
When the furnace is installed in the horizontal right position, the
factory
−
installed trap will be located at the bottom left corner of
the collector box. When the furnace is installed in the horizontal
left position, the factory
−
installed trap will be located at the top
of the collector box. The trap must be repositioned on the
collector box for proper condensate drainage.
When the furnace is installed as a direct vent furnace, a field
supplied, accessory Horizontal Installation Kit is required for all
horizontal installations. The kit contains a rubber casing
grommet designed to seal between the furnace casing and the
condensate trap. (See